﻿<?xml version="1.0" encoding="UTF-8"?>
<GAEB xmlns="http://www.gaeb.de/GAEB_DA_XML/DA83/3.3">
  <GAEBInfo>
    <Version>3.3</Version>
    <VersDate>2021-05</VersDate>
    <Date>2025-07-01</Date>
    <Time>14:55:16</Time>
    <ProgSystem>CaliforniaX by G&amp;W Software AG</ProgSystem>
    <ProgName>CaliforniaX V25.1.01</ProgName>
    <Certific>Available</Certific>
  </GAEBInfo>
  <PrjInfo>
    <NamePrj>Worms, Mainz</NamePrj>
    <LblPrj>Landesamt für Umwelt Rheinland-Pfalz</LblPrj>
    <Cur>EUR</Cur>
    <CurLbl>Euro</CurLbl>
  </PrjInfo>
  <Award>
    <DP>83</DP>
    <AwardInfo>
      <Cur>EUR</Cur>
      <CurLbl>Euro</CurLbl>
    </AwardInfo>
    <BoQ ID="GW_3053401">
      <BoQInfo>
        <Name>RUSt Mainz</Name>
        <LblBoQ>RUSt Mainz</LblBoQ>
        <Date>2025-07-01</Date>
        <OutlCompl>AllTxt</OutlCompl>
        <BoQBkdn>
          <Type>BoQLevel</Type>
          <Length>2</Length>
          <Num>Yes</Num>
        </BoQBkdn>
        <BoQBkdn>
          <Type>Item</Type>
          <Length>2</Length>
          <Num>Yes</Num>
        </BoQBkdn>
      </BoQInfo>
      <BoQBody>
        <BoQCtgy ID="GW_3053404" RNoPart="1">
          <LblTx>
            <p>
              <span style="background:#FFFFFF;">OS-Hardware</span>
            </p>
          </LblTx>
          <NotApplBoQ>No</NotApplBoQ>
          <BoQBody>
            <Itemlist>
              <PerfDescr ID="GW_3053405">
                <PerfNo>1</PerfNo>
                <PerfLbl>Prozessserver</PerfLbl>
                <Description ID="e38ea59c-f0fb-4dd1-8a11-5ee7abb18a87">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">In der RUSt Mainz-Wiesbaden wird die bestehende Hardware des Prozessservers erneuert. Der Server ist dediziert auszuführen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Für den Prozessserver sind 19'' Rack-Server-Komponenten vorzusehen. Außerdem sind redundante Netzteile mit Hot-Plug-Funktion zu wählen. Der Server ist in einem bauseits vorhandenen Server-/ Netzwerkschrank zu installieren. Die genaue Spezifikation des Schranks und der Einbauorte sind mit dem Auftraggeber vorab zu klären und zu berücksichtigen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die nachfolgende Spezifikation ist als Mindeststandard anzuwenden und dient als Richtwert. Eine höherwertige oder umfangreichere Ausstattung ist zugelassen. Die endgültige Auslegung liegt beim Auftragnehmer, da sie erst nach der Wahl eines SCADA-Systems endgültig durchgeführt werden kann. Die Herstellervorgaben des angebotenen SCADA-Systems sind zwingend zu berücksichtigen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Der Prozessserver wird gleichzeitig als Client für das Prozessleitsystem genutzt. Alle daraus resultierenden Anforderungen, wie entsprechende Anschlüsse für Ein- und Ausgabegeräte sind zu berücksichtigen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Um bei den Umbauarbeiten einen weitestgehend unterbrechungsfreien Betrieb der Anlage gewährleisten zu können, ist der neue Server parallel zu den vorhandenen Hardwarekomponenten zu installieren.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Für alle Komponenten des Servers ist eine Herstellergarantie von 5 Jahren inkl. Hardwaresupport vor Ort, mit Austausch am nächsten Arbeitstag, zu berücksichtigen.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Prozessserver</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </PerfDescr>
              <Item ID="GW_3053407" RNoPart="1">
                <RefPerfNo IDRef="GW_3053405" />
                <Qty>1.000</Qty>
                <QU>St</QU>
                <Description ID="7741d2e5-3262-4165-961d-dc43ff9ee415">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Prozessserver</span>
                        </p>
                        <p />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Gehäusetyp		: Rackeinbau 19"</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;">
                          <span style="background:#FFFFFF;">Höheneinheiten </span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">(Planungsgrundlage)		: max. 2 HE</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Speicherlaufwerksarchitektur	: 3,5" Hot-Plug-SAS</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Stromversorgung		: redundant mit Hot-Plug-</span>
                          <br />
                          <span style="background:#FFFFFF;">Funktionalität</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">Prozessor			: mind. 1 Stück Server-Mehrkernprozessor mit mind. 4 Kernen je Prozessor</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Taktfrequenz		: mind. 3,70 GHz/4,10 GHz</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">Speicher			: mind. 16 GB (DDR4) </span>
                          <br />
                          <span style="background:#FFFFFF;">ausbaufähig</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Anzahl Laufwerksschächte	: mind. 8 x 3,5" Hot-Plug-fähig</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Steckplätze (mind.)		: mind. 2 x PCI EXPRESS 3.0 x8</span>
                          <br />
                          <span style="background:#FFFFFF;">mind. 2 x PCI EXPRESS 3.0 x16</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">DVD-Laufwerk		: mind. DVD-ROM (16x DVD; 48x CD)</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Schnittstellen		: mind. 5 x USB 2.0</span>
                          <br />
                          <span style="background:#FFFFFF;">mind. 2 x DisplayPort oder HDMI</span>
                          <br />
                          <span style="background:#FFFFFF;">mind. 8 x 10/100/1 000 Mbit/s Ethernet</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">RAID-Controller		: SAS-Controller 8 Ports, 6 GB/s</span>
                          <br />
                          <span style="background:#FFFFFF;">RAID-Level 0, 1, 5, 10</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Speicherlaufwerk		: mind. 4 x SSD SATA, 6 GB/s (als 3,5" oder 2,5" mit 3,5" Einsatz)</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Kapazität je SSD		: mind. 480 GB, 6 GB/s, Hot-Plug</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Betriebssystemunterstützung	: Windows 10</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">			  Windows 11</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">			  Windows-Server 2019</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">			  Windows-Server 2022</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Herstellergarantie von 5 Jahren inkl. Hardwaresupport vor Ort, mit Austausch am nächsten Arbeitstag.</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Bieterangaben</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="faf9e6e2-2cb9-41f9-bcb3-8ea2ddfbbca9" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Höheneinheiten		: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail>
                          <span style="background:#FFFFFF;"> HE</span>
                        </ComplTail>
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="88a69840-19b6-4881-9954-0d6eab9c4c03" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Prozessorhersteller		: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="83b82649-bd8a-4ec7-a40e-c8a7f2eae304" Kind="Bidder" MarkLbl="62" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ			: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="cffd4115-4574-4fd6-b471-cb8472eecfce" Kind="Bidder" MarkLbl="63" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Anzahl CPU-Kerne		: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="88f20924-9cca-4a60-b74e-e1935fd38b37" Kind="Bidder" MarkLbl="64" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Taktfrequenz		: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="7f580c2d-9227-432d-9387-c1a65c8f7d8e" Kind="Bidder" MarkLbl="65" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller Serversystem	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="dba0e6cf-1090-45f1-884e-55416112c42a" Kind="Bidder" MarkLbl="66" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ Serversystem		: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">inkl. Lieferung und betriebsbereiter Installation</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Prozessserver</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053412" RNoPart="2">
                <RefPerfNo IDRef="GW_3053405" />
                <Qty>1.000</Qty>
                <QU>St</QU>
                <Description ID="02512fb4-e1da-4a22-8b12-71e55e4bbb75">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Maus- und Tastatur-Set</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">bestehend aus:</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">PC-Maus mit optischer Abtastung der Oberfläche</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Abtastung der Oberfläche mindestens durch zwei 800 dpi-Sensoren.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Funktionen:</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">2 Tasten oben</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">1 Daumentaste</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">Scrollrad zur einfachen Bildnavigation</span>
                        </p>
                        <p />
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Anschluss	: USB</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Industrie-Tastatur</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Standard deutsches Tastaturlayout mit 105 Tasten inkl. Windows-Funktionstasten und nummerischem Tastenblock</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">gelaserter, abriebfester Tastaturaufdruck</span>
                        </p>
                        <p />
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Anschluss	: USB</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">komplettes Set inkl. Anschlusskabel, inkl. Lieferung</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Maus- und Tastatur-Set</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053413" RNoPart="3">
                <RefPerfNo IDRef="GW_3053405" />
                <Qty>2.000</Qty>
                <QU>St</QU>
                <Description ID="8bd41d35-61f1-49dc-9f01-6f9220c85fd0">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">TFT-Flachbildschirm 27"</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">mit Digital- und Analog-Schnittstellen</span>
                        </p>
                        <p />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Displaytyp TFT		: ≥ 27", 68,4 cm Wide, nicht spiegelnd</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;">
                          <span style="background:#FFFFFF;">max. 2 Pixelfehler je 1 Mio Pixel</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">MTBF 			: ≥ 50 000 h</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">Nutzung			: für Dauerbetrieb geeignet</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Betrachtungswinkel		: ≥ 178 Grad horizontal</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">			  ≥ 178 Grad vertikal</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Leuchtstärke		: ≥ 350 cd/m²</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">Kontrast			: ≥ 1 000:1</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">darstellbare Farben		: ≥ 16,7 Mio.</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">optimale Auflösung		: ≥ 2 560 x 1 440 bei mind. 60 Hz</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Anschluss digital		: Display-Port und HDMI Anschluss</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">USB Hub			: 1 Up-/2 Downstream, USB 3.0</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Beweglichkeit		: 172° rechts/links, -5° nach vorne, </span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">			: 35° nach hinten, 90° drehbar, </span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">			: 15,5 cm Höhenverstellung</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Durch VESA-genormte Befestigungsmöglichkeit montierbar.</span>
                        </p>
                        <p />
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Leistungsaufnahme Betrieb	: ≤ 30 W max.</span>
                        </p>
                        <p style="tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">im Sparmodus 		: ≤ 0,5 W</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">Intelligentes Power Management nach VESA/EPA/NUTEK abschaltbar</span>
                        </p>
                        <p />
                        <p style="tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Sicherheit/Ergonomie		: CE; TÜV GS; TÜV ERGONOMIE</span>
                        </p>
                        <p style="tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">			  ISO 9241-307; TCO 7</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">inkl. Netzkabel, Signalkabel DP und HDMI, Höhe und Winkel ergonomisch optimiert einstellen</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="bd464890-cfa5-428b-8f90-16bdea53f9ed" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="809329f9-8811-4f1a-b9fb-644f7aaf83ac" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">inkl. Lieferung</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">TFT-Flachbildschirm 27"</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053414" RNoPart="4">
                <RefPerfNo IDRef="GW_3053405" />
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="ef8ab62e-92be-4138-acac-9209755651b2">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Provisorischer Aufbau der PC-Komponenten</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Verkabelung (Leistung und Netzwerk) zu den Netzwerkschränken und USV-Verteilungen herstellen (Kabel und Anschlüsse werden nach den entsprechenden Einheitspreispositionen vergütet)</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Einbau der Server- und Netzwerksysteme in die neuen 19"-Racksysteme</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Installation des Servers inkl. Monitore und Maus- und Tastatur-Set</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   nach Beendigung des Probebetriebs Demontage der auszutauschenden PC- und Netzwerkkomponenten (Server, Switches) aus den bestehenden Schränken</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Übergabe der demontierten Komponenten an den Auftrageber</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Provisorischer Aufbau der PC-Komponenten</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <PerfDescr ID="GW_3263316">
                <PerfNo>2</PerfNo>
                <PerfLbl>Datensicherung</PerfLbl>
                <Description ID="db40b553-dd40-4b36-8a71-f7c988fc1ff4">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Zur zentralen Ablage von Sicherheitskopien, insbesondere des Projekts des SCADA-Systems, wird ein NAS installiert.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Über automatische Routinen eines Datensicherungsprogramms sollen hier Daten abgelegt werden, die bei Bedarf zur vollständigen Wiederherstellung des Systems genutzt werden können.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Für den NAS sind 19'' Rack-Komponenten vorzusehen. Er ist in einem bauseits vorhandenen Server-/ Netzwerkschrank zu installieren. Die genaue Spezifikation des Schranks und der Einbauorte sind mit dem Auftraggeber vorab zu klären und zu berücksichtigen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Für alle Komponenten des NAS ist eine Herstellergarantie von 5 Jahren inkl. Hardwaresupport vor Ort, mit Austausch am nächsten Arbeitstag, zu berücksichtigen.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Datensicherung</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </PerfDescr>
              <Item ID="GW_3053415" RNoPart="5">
                <RefPerfNo IDRef="GW_3263316" />
                <Qty>1.000</Qty>
                <QU>St</QU>
                <Description ID="946e82e1-24fb-4710-9cc0-b7a506c5bfde">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">NAS-Storage Datensicherung (19'')</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">für automatisierte Backup- und Archivierungsaufgaben, installiert in separatem Gehäuse für 19"-Einbau, eingerichtet für die automatisierte und manuelle Sicherung der gelieferten PCs, zum Einbau in die 19"-Serverschränke.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Einschubgehäuse 19", ca. 2 HE</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Ausstattung</span>
                        </p>
                        <p />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Festplattenbestückung		: mind. 4 Stück, je 4 TB NAS-HDD für 24/7-Betrieb; Hot-Swap</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Netzwerkanschlüsse		: mind. 2 x 1 Gbit RJ45</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Spannungsversorgung		: redundantes Netzteil 230 V AC</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Statusanzeige		: mind. 1 je Datenträger</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Unterstützung von Windows 10/11 und Windows Server 2019/2022; inkl. Client-Backup-Software; RAID 0/1/5.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Ethernet-Schnittstelle mit integriertem, Web-basierendem Management</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="77b066c7-669d-4cd9-9cab-62e866d41542" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="709828a2-0166-40fa-b523-29c2bf1fa855" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">inklusive Netzkabel, kompletter Backup-Software für die gelieferten Windows Betriebssysteme, mit InstantRecovery-Funktion zur Datenrettung und -wiederherstellung. Liefern und komplett einrichten für alle gelieferten PC-Systeme.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">NAS-Storage Datensicherung (19'')</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
            </Itemlist>
          </BoQBody>
        </BoQCtgy>
        <BoQCtgy ID="GW_3053418" RNoPart="2">
          <LblTx>
            <p>
              <span style="background:#FFFFFF;">OS-Software und Systemzubehör</span>
            </p>
          </LblTx>
          <NotApplBoQ>No</NotApplBoQ>
          <BoQBody>
            <Itemlist>
              <PerfDescr ID="GW_3053419">
                <PerfNo>3</PerfNo>
                <PerfLbl>Lieferung Basis-Software</PerfLbl>
                <Description ID="54bbefed-f1f7-4bad-aa6f-2f3c73554db5">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Im Rahmen des Server- und Client-Rollouts sind das Betriebssystem, die eingesetzten Softwareprodukte und das gesamte Leitsystem zu erneuern. </span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die erforderlichen Lizenzen für die Betriebssystemumgebung des Servers sind vom Auftragnehmer zu beschaffen und zu installieren, sofern diese nicht bereits vorinstalliert auf der Hardware geliefert werden.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Auf dem Server, der gleichzeitig als Client dient, soll Microsoft Windows 11 eingesetzt werden, sofern die Anforderungen des angebotenen SCADA-Systems dies zulassen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Weiter sind die Anwenderprogramme aus Microsoft Office und einer PDF-Software zu beschaffen und auf dem Gerät zu installieren.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Lieferung Basis-Software</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </PerfDescr>
              <Item ID="GW_3053422" RNoPart="1">
                <RefPerfNo IDRef="GW_3053419" />
                <Qty>1.000</Qty>
                <QU>St</QU>
                <Description ID="50416454-529f-49ea-a0a1-1767fc20a9ea">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Betriebssystemlieferung Microsoft Windows 11 Pro</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">-   Basislizenz für einen Client-Rechner</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   für das angebotene SCADA-System freigegeben</span>
                        </p>
                        <p />
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Hersteller	: Microsoft</span>
                        </p>
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Typ	: Windows 11 Pro</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">oder gleichwertig</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="85d662ae-61f4-48bc-962e-d0554c12f19f" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="1757fd8f-a48c-4177-8d8f-2982df77d4f5" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Betriebssystemlieferung Microsoft Windows 11 Pro</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053423" RNoPart="2">
                <RefPerfNo IDRef="GW_3053419" />
                <Qty>1.000</Qty>
                <QU>St</QU>
                <Description ID="0918b260-5eea-4018-8e33-618d4a3b28c4">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Microsoft Office-Paket mit Word/Excel (keine Abo-Version)</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">-   aktuelle Version</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   für das gewählte Betriebssystem des Server/ Client-Rechners</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="cf58bfd4-0e1a-486d-8dc6-9617d0b20c3d" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="b15a7301-2e63-40a1-810e-e07fcd35f736" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Lizenz liefern und betriebsbereit auf gelieferter Hardware installieren</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Microsoft Office-Paket mit Word/Excel (keine Abo-Version)</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053424" RNoPart="3">
                <RefPerfNo IDRef="GW_3053419" />
                <Qty>1.000</Qty>
                <QU>St</QU>
                <Description ID="44c9333b-96d1-4619-96c9-a1c5aa3456cd">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">PDF-Software (Vollversion, keine Abo-Version)</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">-   aktuelle Version</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   für das gewählte Betriebssystem der Client-Rechner</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   zum Öffnen/ Anzeigen von Dateien im pdf-Format</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   zum Erstellen von Dateien im pdf-Format</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="7e0b6b1f-6ff2-4375-a41b-fbb455a463cb" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="2526588a-1c71-47ee-9228-ada2844e2ac2" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Lizenz liefern und betriebsbereit auf Client-Hardware installieren</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">PDF-Software (Vollversion, keine Abo-Version)</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <PerfDescr ID="GW_3053425">
                <PerfNo>4</PerfNo>
                <PerfLbl>Lieferung Software SCADA-System</PerfLbl>
                <Description ID="665bbaec-c130-4b12-a517-6b32e65e604d">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Als SCADA-System ist ein für den Bereich "Wasser und Abwasser" branchenübliches Fabrikat auf HTML 5-Basis anzubieten. Das System wird auf einem dedizierten Server installiert, der gleichzeitig als Client dient.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die Schnittstelle zu der Automatisierungsebene bildet eine Siemens SIMATIC S7-1500. Das angebotene SCADA-System muss die dafür notwendigen Treiber zur Verfügung stellen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die primären Aufgaben des Systems sind die zentrale Überwachung der RUSt Mainz-Wiesbaden durch erfassen, verarbeiten und visualisieren von Prozess- und Maschinendaten und dem daraus resultierenden steuern der Anlage. Um diese Funktion des SCADA-Systems erfüllen zu können, muss es mindestens die folgenden Eigenschaften erfüllen:</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Basiseigenschaften</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   24/7-Support, deutschsprachig, qualifiziert</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Angebot umfangreicher Schulungen des Herstellers in Deutschland, im eigenen Haus oder vor Ort</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Bedienoberflächen komplett in deutscher Sprache</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Dokumentation komplett in deutscher Sprache</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Engineering und Support herstellerunabhängig (&gt; 80 zertifizierte Systemintegratoren in Deutschland)</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Gewährleistung von Updates und Fehlerbehebungen während des Produktlebenszyklus</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Freigabe für die Betriebssysteme Windows Server 2019/2022 und Windows 10/11</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   reine Webtechnologie/ native HTML 5-Webtechnologie</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Clients (auch mobil) benötigen nur aktuellen Webbrowser und keine Plugins (Java, Silverlight, Active-X etc.) für vollen Funktionsumfang</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   hochskalierbar</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Multiclientfähig</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   modularer Aufbau der Software zur einfachen Funktionserweiterung</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Unterstützung aller aktuellen Standard-Kommunikationswege wie OPC-Client-Funktion (OPC-DA und -UA), Standard SPS-Kommunikationstreiber (IEC-60870-5-101 und -104-Protokolle)</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   rollenbasierte, individuelle (bzgl. Benutzer und Anlagenteile) Benutzerrechteverwaltung</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   alle systemrelevanten Prozesse serverseitig</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   keine Programmierkenntnisse zur Bedienung und Projektierung nötig</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Standard-Lizenzsoftware mit weiter Verbreitung (&gt; 3 000 aktive Lizenzen)</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   alle nötigen leittechnischen Funktionen beinhaltet (keine heterogenen Lösungen)</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Bereitschaftspläne</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   (Langzeit-)Archivierung</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Berichtswesen</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Wartungsmanagement</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Erfassung und Verarbeitung von Handwerten (z. B. Labormessungen)</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Prozessserver vollständig redundant für Cold- oder Hot-Standby aufbaubar</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Wasser-/ Abwassertechnische Eigenschaften</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Bereitstellung von branchenüblichen Objekt-Bibliotheken (Prozessbilddarstellung)</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Betriebstagebuch</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Engineering</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   integrierter, moderner Bildeditor zum Erstellen von svg- und xml-Dateien</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Visualisierung</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Zoom-Funktion (via Gestensteuerung oder Maus-Scrollrad), bei der ab Erreichen eines definierten Zoom-Niveaus Details ein- bzw. ausgeblendet werden</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   keine Verpixelung bei hohem Zoomlevel</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Anzeige in individuell angepassten Dashboards möglich, einfach durch Anwender erstellbar</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Funktionen für Dashboard: einfache Diagrammelemente, Analoganzeigen, Archivdaten in Tabellenform, freie Textfelder</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Sicherheit</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   keine hardcodierten, aktiven Zugänge</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Verbindung zwischen Client und Server zertifikatsbasiert verschlüsselt (SSL/TLS)</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   2-Faktor-Authentifizierung</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Passwortrichtlinien</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Schutz vor Brute-Force-Attacken</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Nutzung vorhandener Active Directory (Windows Domäne)</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Lieferung Software SCADA-System</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </PerfDescr>
              <Item ID="GW_3053427" RNoPart="4">
                <RefPerfNo IDRef="GW_3053425" />
                <Qty>1.000</Qty>
                <QU>St</QU>
                <Description ID="2537675a-73a6-4827-991a-a61c97766e9d">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">SCADA-System auf HTML 5-Basis</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">An das SCADA-System sind folgende Anforderungen gestellt und sind von der angebotenen Lizenz abzudecken:</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Systemgröße mind. 500 Prozessvariablen</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   mind. 3 zeitgleiche Zugriffe durch externe Clients (Bedienplatz) und Server (Konfiguration)</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Microsoft SQL-Server Standard Edition Runtime als Datenbank</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Microsoft SQL-Server CAL</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   integrierter, moderner Bildeditor zum Erstellen von svg- und xml-Dateien</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Anzeige in individuell angepassten Dashboards möglich, einfach durch Anwender erstellbar</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Integriertes (Excel-)Berichtswesen</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Siemens S7-Kopplung per TCP/IP</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Systembibliothek</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Meldearchiv (unlimitiert)</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   OPC-DA- und UA-Client</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   grafische Darstellung von Werten (Kurven, Diagramme etc.)</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   dynamischer Datenaustausch mit anderen Programmen in beiden Richtungen über OPC-Server</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Alarmierung (per SMS und E-Mail ohne gesonderte Hardware)</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Benutzeroberfläche grafisch, fensterorientiert, mausgeführt</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="23197038-f5fe-487c-82ba-9f273b5ac38b" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="eacef4a3-f7ed-4c52-ab05-125472cbb760" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">SCADA-System auf HTML 5-Basis</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Remark ID="GW_3053428">
                <Description ID="6104c0c0-9a3f-4ede-8556-28ca2eb20fad">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Sonstige Softwarekomponenten</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="text-decoration:underline;background:#FFFFFF;">Sonstige Softwarekomponenten</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Remark>
              <Item ID="GW_3053429" RNoPart="5">
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="8ae37118-6772-44c0-a40c-beeded373148">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Virenscanner mit zentraler Verwaltungs- und Verteilungsfunktion</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Für das angebotene SCADA-System freigegebene Virenscan-Software mit zentraler Verwaltungskonsole, installiert auf VM auf einem virtualisierten Server-System.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Umfang:</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   zentrales, automatisches Einspielen der aktuellen Virendefinition und Verteilung auf alle Antivirenclients</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Antivirenclients für alle PC-Komponenten des Lieferumfangs</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   laufende Aktualisierung der Virendefinition bis zur Abnahme</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">inkl. Lieferung</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="a129ba58-07fc-4a89-b3a3-4160eba22810" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="e1c68b34-3037-40a5-98a9-3b7996ca17eb" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Virenscanner</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053430" RNoPart="6">
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="81599efc-3f0e-4f7c-bfa5-61830cd6cb8f">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Lieferung einer für das angebotene SCADA-System freigegebenen Whitelistening-Sicherheitssoftware</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Erstellung einer Positivliste der als unbedenklich einzustufenden Anwendungen/ Applikationen</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Unterstützung eines dynamischen Vertrauensmodells</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   inkl. Schutz vor Buffer-Overflow</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Aktualisierungen durch vertrauenswürdige Benutzer, Hersteller, Verzeichnisse, Binärdateien, Updater, z. B. Virenscanner</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Installation und Einrichtung eines zentralen Verwaltungsservers</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Lieferung der erforderlichen Anzahl an Agents für die PC-Systeme</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">inkl. Lieferung</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="6a16d44d-564d-4cbd-8f14-e4fc8e90c705" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="7da273aa-425b-41ad-8bab-8cf2b48076e7" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Whitelistening-Sicherheitssoftware</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053431" RNoPart="7">
                <Qty>1.000</Qty>
                <QU>St</QU>
                <Description ID="2d7ee568-44e3-4bfa-8092-294a2192d599">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Datensicherungssoftware</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">zur Speicherung auf externen NAS-Laufwerken, Datenservern und RDX-Laufwerk (Disk to Disk to Tape-Strategie)</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">-   2-in-1: Backup und Replikation</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   synthetische Full-Backups</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   integrierte Deduplizierung und Komprimierung</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Near-Continuous Data Protection</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Bereitstellung mehrerer Backup-Proxy-Server</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   intelligenter Lastausgleich</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   1-Click File Restore</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   ESXi-zentrische Verarbeitungs-Engine</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Backup-Repositories</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Windows Smart Target</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   höhere Skalierbarkeit von vPower</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   optimierter Abruf von Quelldaten</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   geringere Beanspruchung der CPU</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Traffic-Drosselung</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   mehrere IP-Verbindungen pro Vorgang</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   WAN-Optimierungen</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Ausschluss von Swap-Dateien</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   parallele Backups und Replikation</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   erweiterte Kompatibilität mit Deduplizierungsspeicher</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Hot Add-Replikation</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   vollständige DVS-Unterstützung</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Lizenzierung für die ausgeschriebene Anzahl von Systemen</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Einrichtung der Serversoftware für automatisiertes Backup aller angebotenen Server</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Erarbeitung eines Datensicherungskonzepts in Absprache mit dem Auftraggeber. Die Umsetzung des Datensicherungskonzeptes ist in der Pflichtenheftphase ausführlich zu beschreiben.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Liefern, installieren und einrichten auf dem Server</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="8ca59b22-2654-465e-a337-a122e7ed8ea8" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="1c0ffeab-2da2-4e76-9614-e64b566becf9" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Datensicherungssoftware</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3091637" RNoPart="8">
                <Qty>1.000</Qty>
                <QU>St</QU>
                <Description ID="8b46e9c0-de57-4c9a-b3d5-5f26e7aebb90">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">SIMATIC STEP 7 Professional V19/2021 SR2 Combo inkl. TIA Portal</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Download-Lizenz </span>
                        </p>
                        <p />
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Hersteller	: Siemens</span>
                        </p>
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Typ	: SIMATIC STEP 7 Professional, V19/2021</span>
                        </p>
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">	  (TIA PORTAL+SIMATIC Manager) </span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">inkl. aktuellem Servicepack</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Software auf dem Server installieren und einrichten.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Liefern, installieren, parametrieren und in Betrieb nehmen.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">SIMATIC STEP 7 Professional V19/2021 SR2 Combo inkl. TIA Portal</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
            </Itemlist>
          </BoQBody>
        </BoQCtgy>
        <BoQCtgy ID="GW_3053432" RNoPart="3">
          <LblTx>
            <p>
              <span style="background:#FFFFFF;">Installation grundlegender Software</span>
            </p>
          </LblTx>
          <NotApplBoQ>No</NotApplBoQ>
          <BoQBody>
            <Itemlist>
              <PerfDescr ID="GW_3053433">
                <PerfNo>5</PerfNo>
                <PerfLbl>Einrichtung des Prozessservers</PerfLbl>
                <Description ID="68815737-5b83-4641-9113-3f6c9f9c4036">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Der Prozessserver ist zu installieren und betriebsbereit einzurichten. Dazu gehören insbesondere die Einrichtung des Betriebssystems sowie der SCADA-Software, der Engineering-Software und den Programmen zur Datensicherung, des Virenschutzes und des Whitelistings.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Änderungen am grundsätzlichen Aufbau, wie z. B. die Nutzung von Active Directory, Benutzerrechte, IP-Adressen, Rechnernamen usw. werden im Zuge der beschriebenen Hard- und Softwareaktualisierung durchgeführt. Bei der Betriebssystem- und Softwareinstallation ist ein "Hardening" durchzuführen, bei dem alle nicht benötigten Softwarebestandteile bzw. -funktionen entfernt werden. Die Analyse der vorhandenen Strukturen, Parameter, Betriebssysteme sind im Rahmen der technischen Klärung aus den vorhandenen Systemen auszulesen und anschließend auszuwerten, um die betriebsbereite Neuinstallation und Integration in die vorhandene IT-Struktur inkl. vollständige Domaineneinbindung durchführen zu können.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Einrichtung des Prozessservers</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </PerfDescr>
              <Item ID="GW_3053435" RNoPart="1">
                <RefPerfNo IDRef="GW_3053433" />
                <Qty>1.000</Qty>
                <QU>St</QU>
                <Description ID="549d49a8-e740-4427-a8e4-9f8ebe83dbbd">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Betriebssystemeinrichtung Microsoft Windows 11</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Installation und Einrichtung für einen Server.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Betriebssystemeinrichtung Microsoft Windows 11</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053436" RNoPart="2">
                <RefPerfNo IDRef="GW_3053433" />
                <Qty>1.000</Qty>
                <QU>St</QU>
                <Description ID="6fe8969c-0f91-4349-b957-7eed981bb60e">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Installation und Einrichtung Prozessserver</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Einrichtung eines Prozessservers des angebotenen SCADA-Systems auf geliefertem Server, inkl. der vollständigen Grundinstallation des SCADA-Systems.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Installation und Einrichtung Prozessserver</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053437" RNoPart="3">
                <RefPerfNo IDRef="GW_3053433" />
                <Qty>1.000</Qty>
                <QU>St</QU>
                <Description ID="788dfe23-6cfa-4b8a-87d8-77196e45ac5b">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Installation und Einrichtung STEP 7, TIA Portal</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Installation und Einrichtung der STEP 7-Software und ggf. dazugehöriger Softwarepakete auf dem gelieferten Server.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Installation und Einrichtung STEP7, TIA Portal</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053438" RNoPart="4">
                <RefPerfNo IDRef="GW_3053433" />
                <Qty>1.000</Qty>
                <QU>St</QU>
                <Description ID="e4877136-b81e-4f02-8a0a-a4dd9c50f3c5">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Installation und Einrichtung Datensicherung</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die Grundsoftware zur Datensicherung und den notwendigen Agent auf dem gelieferten Server installieren und einrichten.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Installation und Einrichtung Datensicherung</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053439" RNoPart="5">
                <RefPerfNo IDRef="GW_3053433" />
                <Qty>1.000</Qty>
                <QU>St</QU>
                <Description ID="37a6eba1-1e4d-4bb8-9d2d-184baef815f6">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Installation und Einrichtung Virenscaner</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Installation und Einrichtung des Virenscaners auf geliefertem Server nach Vorgaben des angebotenen SCADA-Systems.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Installation und Einrichtung Virenscaner</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053440" RNoPart="6">
                <RefPerfNo IDRef="GW_3053433" />
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="7900eb13-a6a1-4c07-91ea-bc978bd5044b">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Installation und Einrichtung Whitelisting</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Installation und Einrichtung des Whitelisting auf geliefertem Server nach den Vorgaben des angebotenen SCADA-Systems.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Grundkonfiguration für hohe Sicherheit bei uneingeschränkter Verfügbarkeit und schrittweises Vervollständigen des Whitelistings bis zur Abnahme.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Installation und Einrichtung Whitelisting</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
            </Itemlist>
          </BoQBody>
        </BoQCtgy>
        <BoQCtgy ID="GW_3053448" RNoPart="4">
          <LblTx>
            <p>
              <span style="background:#FFFFFF;">OS-Projektierung</span>
            </p>
          </LblTx>
          <NotApplBoQ>No</NotApplBoQ>
          <BoQBody>
            <Itemlist>
              <PerfDescr ID="GW_3053449">
                <PerfNo>6</PerfNo>
                <PerfLbl>Projektierung Leittechnik</PerfLbl>
                <Description ID="eadf8d80-5dd0-45ef-a558-4a8ee469bace">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Das vorhandene PLS InTouch der RUSt Mainz-Wiesbaden soll von einem branchenüblichen SCADA-System auf HTML 5-Basis abgelöst werden. Die vorhandene Software-SPS InControl wird durch eine SIMATIC S7-1500 ersetzt und mit dem neuen SCADA-System verbunden. Das angebotene SCADA-System soll funktionsdeckend zu der bisherigen InTouch-Installation eingerichtet werden. Zur Sicherstellung der erfolgreichen Umstellung müssen alle relevanten Daten des Bestandssystems vorliegen. Dafür ist im Vorfeld der Umstellung eine umfassende Analyse des InTouch-Systems durchzuführen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Folgender Ablauf der Hochrüstung, Zusammenführung und Inbetriebnahme ist geplant:</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Analyse von InTouch hinsichtlich der Datenstruktur und der Anbindung, ohne dabei den Betrieb zu beeinflussen. Zudem wird die Anbindung der Software-SPS analysiert, um die Erneuerung durch eine SIMATIC S7-1500 vollumfänglich realisieren zu können.</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;" />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Nach Abschluss der notwendigen Analyse wird das angebotene SCADA-System auf dem neuen Prozessserver eingerichtet.</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;" />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Der neue Prozessserver wird in dem bauseits gestellten Server/ Netzwerkschrank parallel zum Bestand montiert und angeschlossen.</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;" />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Installation der Netzwerkkomponenten des Lieferumfangs.</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;" />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Inbetriebnahme der IT-Infrastruktur.</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;" />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Sukzessive Inbetriebnahme der OS-Bedienebene und -Infrastruktur ohne Kopplung zu dem Automatisierungsgerät.</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;" />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Das Automatisierungsgerät wird angebunden.</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;" />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Nach dem erfolgreichen Abschluss eines 4-wöchigen Probebetriebs erfolgt der Rückbau des Altsystems.</span>
                        </p>
                        <p />
                        <p>
                          <span style="font-weight:bold;background:#FFFFFF;">Anmerkung:</span>
                          <span style="background:#FFFFFF;"> Die vorab beschriebene Reihenfolge kann geändert und ergänzt werden, sofern es aus Sicht des Auftragnehmers dafür nachvollziehbare technische Gründe gibt. Die Wahl bzw. eine nachträgliche Änderung der richtigen Vorgehensweise liegt ausschließlich aufgrund der spezifischen Systemkenntnisse bzw. dessen Erfahrungshorizontes im Verantwortungsbereich des Auftragnehmers. Die Anerkennung von Mehrforderungen aufgrund einer nachträglichen Änderung der beschriebenen oder kalkulierten Vorgehensweise ist ausgeschlossen.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Projektierung Leittechnik</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </PerfDescr>
              <Item ID="GW_3053451" RNoPart="1">
                <RefPerfNo IDRef="GW_3053449" />
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="9707be46-7c46-4512-9214-1d5d8af28e66">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Analyse Bestands-PLS "InTouch"</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Analyse des vorhandenen Leitsystems zur PLS-Umstellung und Neuprojektierung des Projektes, der Prozessbilder und Objekte</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Im Wesentlichen bestehend aus:</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Auslesen der vorhandenen Leitsystem-Konfiguration des Auftraggebers mit Programmiergeräten und Software des Anbieters, bauseitige Leistungen werden nicht durchgeführt</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Analyse der ausgelesenen Objekte</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Analyse der Datenstruktur</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Analyse der Datenanbindung der Prozessbilder</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   sowie alle weiteren, notwendigen Analysen, die zum bestimmungsgemäßen Betrieb des Gesamtsystems notwendig sind</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Analyse Bestands-PLS "InTouch"</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053452" RNoPart="2">
                <RefPerfNo IDRef="GW_3053449" />
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="9cd4ee05-6c83-4890-a5a5-0e3ad1c5db15">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Umstellung PLS von InTouch auf neues SCADA-System</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Für die Umstellung des PLS von InTouch auf das angebotene SCADA-System auf HTML 5-Basis sind alle erforderlichen Engineering-Leistungen zu erbringen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Komplette Leittechnik-Projektierung des zu installierenden Systems bestehend aus:</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">-   Prozessserver </span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Clientsystem auf Prozessserver</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die Leittechnik umfasst dabei alle Komponenten/ Software-Pakete die in der Position des SCADA-Systems in diesem Leistungsverzeichnis als Anforderungen definiert und für deren Umsetzung notwendig sind.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Hierzu zählen:</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Installation auf neuem Windows-System</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Installation der Datenbank des v. g. SCADA-Systems</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Einrichtung aller Funktionen des Leitsystems gemäß Hersteller-Handbuch und entsprechend freigegebenem Pflichtenheft</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   OPC-Kopplungen zum OPC-Server der Automatisierungsgeräte</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   die OPC-Kopplung zu Drittsystemen</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Herstellung der Kopplungen zu anderen Softwarekomponenten</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Definition/ anlegen der Variablenbezeichnung, Meldetexte, Alarmprioritäten</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   manuelle Alarmausblendungen je Alarm konfigurieren</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Grenzwertüberwachungen (Fehler-, Alarm-Grenzen); teilweise mit einstellbarer zeitlicher Verzögerung und Neustart der Zeit bei zwischenzeitlichem Gehen der Meldung</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Definition/ anlegen von Tooltip-Texten für alle Prozessobjekte bzw. </span>
                          <br />
                          <span style="background:#FFFFFF;">-variablen, Funktionen und Bilder</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   anlegen der zu projektierenden Kurvengruppen/ -profile für alle analogen Messwerte, basierend auf dem Bestand</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   anlegen der Ereignisberichte, basierend auf dem Bestand</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Life-Beat-Monitoring</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   weiterleiten von Meldungen aus dem Visualisierungssystem über die Alarmierungskomponente als SMS</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   anlegen/ Projektierung der gesamten Bedienerverwaltung</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Einrichtung der Drucker</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Umsetzung der im Pflichtenheft, dem Vortext des Leistungsverzeichnisses, der leistungsbeschreibung oder im Basis-Engineering beschriebenen bzw. abgestimmten Funktionen</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   sowie alle weiteren, notwendigen Leittechnik-Projektierungen, die zum bestimmungsgemäßen Betrieb des Gesamtsystems beim Auftraggeber notwendig sind</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">als Pauschalfestpreis</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Umstellung PLS von InTouch auf neues SCADA-System</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <PerfDescr ID="GW_3053453">
                <PerfNo>7</PerfNo>
                <PerfLbl>Prozessbilder Leittechnik</PerfLbl>
                <Description ID="4adc3135-1bc2-448e-84e1-c6c14ce6c87c">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Aufgrund der Umstellung des PLS auf ein SCADA-System mit Prozessbildern im svg-Format müssen während des Vorgangs sämtliche Bilder des PLS InTouch konvertiert bzw. nachgezeichnet werden. Gänzlich neue Prozessbilder sind nur in geringem Maß erforderlich. Diese werden auf Grundlage von Fließschemata angefertigt, die durch den Auftraggeber zur Verfügung gestellt werden.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Aufgrund der Grundsätzlichkeit des Neuzeichnens, unabhängig von Bestandsbild oder neuem Bild, werden beide Arbeiten nachfolgend gleichwertig in einer Position definiert. </span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die Gestaltung der Antriebssymbole, Bedienboxen, die Farbgebung und weiterer optischer Elemente erfolgt nach Vorgaben, die im Rahmen der Pflichtenheftphase für die OS-Projektierung neuer Anlagenteile in Absprache mit dem Auftraggeber aufgestellt werden.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Allgemeine Eigenschaften, wie beispielsweise die Farbe eines Mediums, Schriftart und -farbe, sollen zentral, z. B. über die Verknüpfung einer Farbtabelle, verwaltet werden können.</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Bilderstellung/ Funktionsbausteine/ Bedienboxen</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Bei der Bilderstellung ist von folgender Vorgehensweise auszugehen:</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">-   Bildentwurf (Farbausdruck 3-fach)</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Abstimmung mit dem Auftraggeber</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   einbringen gewünschter Korrekturen</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   erneutes Abstimmen mit dem Auftraggeber</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   einbringen evtl. weiterer Korrekturen</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Freigabe der Bilderstellung</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Eine Ausnahme hiervon wird das erste Anlagenbild bzw. der erste Funktionsbaustein oder die erste Bedienbox darstellen. Mit diesen Bildern sollen grundsätzliche Dinge wie die Bildaufteilung, Anzahl und Lage der Meldezeilen, Farben, Symbole usw. mit dem Auftraggeber geklärt werden, sofern diese nicht bereits in der Pflichtenheftphase definiert wurden. Daher ist von einer mehrfachen Änderung dieses Bildes auszugehen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Eine Bildvariable entspricht einem Objekt, d. h. einem Antrieb, einer Messstelle, einem Meldefenster inkl. aller Messwerte, Sollwerte, Meldungen oder Befehle zu diesem Objekt.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Prozessbilder Leittechnik</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </PerfDescr>
              <Item ID="GW_3053455" RNoPart="3">
                <RefPerfNo IDRef="GW_3053453" />
                <Qty>1.000</Qty>
                <QU>St</QU>
                <Description ID="d6488f94-6b50-461b-858d-79ac094d50b9">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Prozessbilderstellung Gesamt-Anlagenübersicht</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die ganze Anlage soll zunächst in einer Gesamtübersicht dargestellt werden. Dieses soll als Zoom-Bild erstellt werden.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Bei dem Prozessbild zur Gesamt-Anlagenübersicht ist das Einblenden von Details ab einem bestimmten Zoom-Grad vorzusehen. Über Verlinkungen sollen Teilanlagenübersichten aus der Gesamt-Anlagenübersicht heraus geöffnet werden können.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Grundsätzlich besteht die Prozessbilderstellung aus folgenden Arbeitsschritten:</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">-   Bilder erstellen (statische und dynamische Objekte)</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Anbindung der zugehörigen Variablen</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Anwahl Teilanlagen</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   ca. 30 Folgebildanwahlpunkte</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   ca. 50 Bildvariablen</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">betriebsbereit konfigurieren, einschließlich Datenpunkttest</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Prozessbilderstellung Gesamt-Anlagenübersicht</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053456" RNoPart="4">
                <RefPerfNo IDRef="GW_3053453" />
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="fa7e7d0a-a7a1-4a0f-8bd4-109444e19f1d">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Prozessbilderstellung</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">inkl. Parameter- und Diagnosebilder</span>
                        </p>
                        <p />
                        <p style="text-indent:-14pt;margin-left:14pt;">
                          <span style="background:#FFFFFF;">-   Bilder zeichnen und revidieren</span>
                        </p>
                        <p style="text-indent:-14pt;margin-left:14pt;">
                          <span style="background:#FFFFFF;">-   Bilder erstellen (statische und dynamische Objekte)</span>
                        </p>
                        <p style="text-indent:-14pt;margin-left:14pt;">
                          <span style="background:#FFFFFF;">-   Anbindung der zugehörigen Variablen (Parametrierung)</span>
                        </p>
                        <p style="text-indent:-14pt;margin-left:14pt;" />
                        <p style="text-indent:-1pt;margin-left:1pt;">
                          <span style="background:#FFFFFF;">Für die Anzeige von Betriebszuständen und erforderlichen Einstellungen zum Verstellen von Parametern mit Textdarstellungen, Grenzwerteingaben, Sollwerten, Anzeige usw. mit grafischer Prozessdarstellung inklusive Instanzierung aller erforderlichen Bausteine.</span>
                        </p>
                        <p style="text-indent:-1pt;margin-left:1pt;" />
                        <p style="text-indent:-1pt;margin-left:1pt;">
                          <span style="background:#FFFFFF;">Sofern bei vorhandenen Symbolen aus der Symbolbibliothek des angebotenen SCADA-Systems Anpassungen notwendig sind, sind diese durchzuführen. </span>
                        </p>
                        <p style="text-indent:-1pt;margin-left:1pt;" />
                        <p>
                          <span style="background:#FFFFFF;">Betriebsbereit konfigurieren, einschließlich Datenpunkttest.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Als Grundlage ist ein Mengengerüst von ca. 10 Bildern, 20 Fensterbildern, 5 Systembibliotheken und 360 Variablen in Bildern anzunehmen.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Prozessbilderstellung</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <PerfDescr ID="GW_4024024">
                <PerfNo>8</PerfNo>
                <PerfLbl>LIMS (Labor-Informations- und Management-System)</PerfLbl>
                <Description ID="1f82856a-18c0-4b64-a97d-b99826205933">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Im Zuge der Erneuerung des Leitsystems ist dieses um Funktionen entsprechend der LIMS-Basierung zu erweitern.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Hierzu zählt insbesondere die Anbindung der unterschiedlichen Herstellergeräte (z. B. DTOX-, ATOX-Messung, Probennehmer) zur Grenzwertvorgabe, Diagnose und Alarmgenerierung.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">LIMS (</span>
                            <span style="color:#1F1F1F;">Labor-Informations- und Management-System)</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </PerfDescr>
              <Item ID="GW_4024026" RNoPart="5">
                <RefPerfNo IDRef="GW_4024024" />
                <Qty>5.000</Qty>
                <QU>St</QU>
                <Description ID="ff9552f0-14c0-4229-819f-02d27e8f2bcd">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Erstellung neuer Alarmindexe</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">In der Regel sind Ereignisse in unterschiedlichen Signalen innerhalb desselben Zeitraums erforderlich, um einen meldepflichtigen Alarm anzuzeigen. Die Ereignisse, die von jedem Sensor ausgehen, werden einem Bewertungssystem unterzogen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Als Beispiel: Die Parameter Wassertemperatur, pH-Wert, Sauerstoffgehalt und Leitfähigkeit werden zur Beurteilung des Zustands der Wasserprobe herangezogen. Eine plötzliche Veränderung der verschiedenen Parameter der Wasserqualität soll erkannt und automatisch bewertet werden. In dieser speziellen Auswertung soll auf eine ungewöhnliche Veränderung im Vergleich zu früheren Daten hingewiesen werden. Jeder Messparameter trägt mit einer bestimmten Anzahl von Punkten zum Alarmindex bei. Das Auftreten einer Alarmmeldung wird durch das Überschreiten eines Schwellenwertes ausgelöst.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Grundsätzlich besteht die Bildung eines Alarmindexes aus folgenden Arbeitsschritten:</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Echtzeitanalyse mehrerer Sensormesswerte zur Erkennung wichtiger Ereignisse </span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Multiparameter-Ereignis-Analysator und -Detektor: Erkennung und Anzeige plötzlicher Messwertänderungen, Korrelationen zu Veränderungen verschiedener Parameter </span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Algorithmen, um Veränderungen in jedem beobachteten Signal zu erkennen inkl. Ober- und Untergrenzenbewertung, statistische Kurzzeitauswertung als Standardabweichung mit und ohne Drifteliminierung, Langzeitauswertung</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">betriebsbereit konfigurieren, einschließlich Datenpunkttest</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Erstellung neuer Alarmindexe</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_4024027" RNoPart="6">
                <RefPerfNo IDRef="GW_4024024" />
                <Qty>100.000</Qty>
                <QU>St</QU>
                <Description ID="f6dd8c56-05d5-44ab-9e85-03e74c2fcabc">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Erstellung von Kontrollkarten zur Eingabe und Speicherung von Wartungsdaten entsprechend der Prüfmethoden nach den AQS-Merkblättern</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Für folgende Kategorien sollten nach AQS Kontrollkarten im Leitsystem angelegt werden:</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Probennahmen</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">-   Arbeitsanweisung und Intervall zu Probennahmen</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Trübenmessung</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">-   Arbeitsanweisung zur Kalibrierung</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Driftkorrektur</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Arbeitsanweisung zur Reinigung</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">SAK-Messung</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">-   Arbeitsanweisung zur Kalibrierung</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Driftkorrektur</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Arbeitsanweisung zur Reinigung</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Sauerstoffmessung</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">-   Arbeitsanweisung zur Kalibrierung</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Driftkorrektur</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Arbeitsanweisung zur Reinigung</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">pH-Messung</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">-   Arbeitsanweisung zur Kalibrierung</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Driftkorrektur</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Arbeitsanweisung zur Reinigung</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Messung elektrische Leitfähigkeit</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">-   Arbeitsanweisung zur Kalibrierung</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Driftkorrektur</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Arbeitsanweisung zur Reinigung</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Messung Temperatur</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">-   Arbeitsanweisung zur Kalibrierung</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Driftkorrektur</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Arbeitsanweisung zur Reinigung</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Daphnientoximeter</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">-   Arbeitsanweisung zur Wartung</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Standardanweisungen</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Algentoximeter</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">-   Arbeitsanweisung zur Wartung</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Standardanweisungen</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Probennehmer (Routine und Ereignisprobennehmer)</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">-   Arbeitsanweisung zur Wartung</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Allgemeiner Kontrollgang</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Protokoll für Rufbereitschaftseinsatz</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Protokolle für Außendienstparameter</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Erstellung Kontrollkarten nach AQS-Merkblättern</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_4024028" RNoPart="7">
                <RefPerfNo IDRef="GW_4024024" />
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="26d09804-b997-49ac-a757-696c9ef1fb28">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Anlegen von Rufbereitschaftsplänen</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Erstellung von Rufbereitschaftsplänen und Alarmierung nach Vorgaben des Auftraggebers</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">als Pauschalfestpreis</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Anlegen von Rufbereitschaftsplänen</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_4024029" RNoPart="8">
                <RefPerfNo IDRef="GW_4024024" />
                <Qty>5.000</Qty>
                <QU>St</QU>
                <Description ID="d01c3a46-ca50-47c7-8698-fc5f5c8d3615">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Prozessbilderstellung für ca. 120 Prozessvariablen, jedoch als reine Parameterbilder zum Verstellen von Sollwerten, Zeiten, Parametern etc. mit Textdarstellungen ohne graphische Prozessdarstellung</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">betriebsbereit konfigurieren, einschließlich Datenpunkttest</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Prozessbilderstellung Parameterbilder</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_4024030" RNoPart="9">
                <RefPerfNo IDRef="GW_4024024" />
                <Qty>3.000</Qty>
                <QU>St</QU>
                <Description ID="5ac52fcc-9534-469b-9439-21e934701a65">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Prozessbilderstellung für ca. 150 Prozessvariablen, als Diagnosebilder für AS, ET 200-Stationen und Profinet-Teilnehmer sowie Herstellergeräte/ -anlagen, grafische Darstellung</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">betriebsbereit konfigurieren, einschließlich Datenpunkttest</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Prozessbilderstellung Diagnosebilder</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <PerfDescr ID="GW_3053457">
                <PerfNo>9</PerfNo>
                <PerfLbl>Protokollierung</PerfLbl>
                <Description ID="b0bc67ff-9ecd-4f9e-bd8d-a9537a8ea131">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Die Prozessdaten werden mit dem im SCADA-System integrierten Protokollierungssystem archiviert und visualisiert.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Das Protokollierungssystem soll fester Bestandteil des angebotenen SCADA-Systems sein und ein Berichtswesen und die Datenarchivierung zentral umsetzen. Die relevanten Informationen sollen über eine Standardschnittstelle zur Verfügung gestellt werden können.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Es müssen Protokolle, Graphen und Meldearchive nach den Vorgaben des Auftraggebers erstellt und Masken zur Handwerteingabe angelegt werden.</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Protokolle</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Anlage von Protokollen in entsprechender Anzahl für die jeweiligen Betriebsanlagen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die Protokolle sind nach Vorlage des Auftraggebers anzufertigen. Es sind Störmelde- und Wartungsprotokolle sowie Tages-, Monats- und Jahresprotokolle zu erstellen. Betriebsprotokolle werden separat abgestimmt. Es ist von einem geringen bis mittleren Informationsumfang auszugehen, der sich aus den Datenpunktlisten ergibt.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Vorstehend beschriebene Protokolle, inkl. aller notwendigen technischen Klärungen und Systemdienstleistungen, erstellen und lauffähig implementieren.</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Graphen</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Anlage von vorgefertigten Graphen in entsprechender Anzahl für die jeweiligen Betriebsanlagen. Diese Graphen sind nach Vorlage anzufertigen. Die Vorgaben für die Graphen werden vom Auftraggeber zur Verfügung gestellt und durchlaufen zur genauen Festlegung einen exemplarischen Revisionsprozess.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Vorstehend beschriebene Graphen, inkl. aller notwendigen technischen Klärungen und Systemdienstleistungen, erstellen und lauffähig implementieren.</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Meldearchiv</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Konfiguration des erweiterten Meldearchivs:</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">Störmeldungen, Betriebsmeldungen erstellen und lauffähig implementieren.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Protokollierung</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </PerfDescr>
              <Item ID="GW_3053459" RNoPart="10">
                <RefPerfNo IDRef="GW_3053457" />
                <Qty>35.000</Qty>
                <QU>St</QU>
                <Description ID="bf04b851-dd70-4e3c-b9f4-def58d3d403f">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Erstellen und Parametrieren von Archiven</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">für die Anzeige und Protokollierung einschließlich Festlegung der Verdichtungsstufen (1 Min., 5 Min., 15 Min., 2 h, Tages-, Monats-, Jahreswerte) für analoge Verfahrensgrößen und Labordaten und anteilig für die Darstellung in Protokollen und Berichten.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Erstellen und Parametrieren von Archiven für die Anzeige</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053460" RNoPart="11">
                <RefPerfNo IDRef="GW_3053457" />
                <Qty>10.000</Qty>
                <QU>St</QU>
                <Description ID="0da9b15a-740b-4ee0-95a4-ed7f4824b1e8">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Nachparametrieren von Verfahrensgrößen</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Nachparametrieren von einzelnen, zusätzlichen Verfahrensgrößen in einem Bericht/ Protokoll nach Freigabe durch den Auftraggeber mit Anpassung des Layouts durch zwischenfügen von Spalten.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Erstellen, parametrieren und testen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Abrechnung erfolgt pro Verfahrensgröße</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Nachparametrieren von Verfahrensgrößen</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3789968" RNoPart="12">
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="1e483d21-3c95-49d7-a7c8-64e704b8fb73">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Anpassung/ Einrichtung Datenübermittlung</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Ein zentraler Datenbankserver in Mainz empfängt und speichert Messwerte mehrerer Gewässerprüfstellen. Dazu dient ein Oracle-Datenbankserver und ADVIS als Frontend. Die Verbindung von den Gewässerprüfstellen zum Datenbankserver wird per VPN und FTP hergestellt. Der Datentransfer erfolgt mittels ODBC.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Im Rahmen der Erneuerung des Leitsystems ist der automatische Datentransfer an den Datenbankserver anzupassen bzw. wieder einzurichten.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Dafür sind der Aufbau der Verbindungsstrecke, die Wertübermittlung sowie alle weiteren für den Datentransfer nötigen Arbeiten zu berücksichtigen</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">als Pauschalfestpreis</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Anpassung/ Einrichtung Datenübermittlung</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
            </Itemlist>
          </BoQBody>
        </BoQCtgy>
        <BoQCtgy ID="GW_3053461" RNoPart="5">
          <LblTx>
            <p>
              <span style="background:#FFFFFF;">Netzwerktechnik</span>
            </p>
          </LblTx>
          <NotApplBoQ>No</NotApplBoQ>
          <BoQBody>
            <Itemlist>
              <PerfDescr ID="GW_3053462">
                <PerfNo>10</PerfNo>
                <PerfLbl>Netzwerkkomponenten</PerfLbl>
                <Description ID="29c4e6d0-567b-4d2d-9e2a-4f82ecc2f4a2">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Um einen unterbrechungsfreien und zukunftssicheren Betrieb gewährleisten zu können, wird ein neuer zentraler Switch in dem bauseitigen Server-/ Netzwerkschrank parallel zu den vorhandenen Hardwarekomponenten installiert. Dieser ist managebar auszuführen um unter anderem VLANs und die damit verbundene Trennung von Terminal- und Anlagenbus einrichten zu können.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Der Switch ist für den Anschluss von RJ45-Steckern und die Verbindung mit Lichtwellenleitern mit LC-Steckern vorzusehen. Ggf. müssen Stecker von bestehenden Lichtwellenleitern geändert werden, um die Konnektivität herstellen zu können.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Inkl. Anschluss aller ankommenden und abgehenden Kabel und Leitungen.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Netzwerkkomponenten</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </PerfDescr>
              <Item ID="GW_3053464" RNoPart="1">
                <RefPerfNo IDRef="GW_3053462" />
                <Qty>1.000</Qty>
                <QU>St</QU>
                <Description ID="f830ab54-a2b9-4679-bf76-86130eeeca74">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Managebarer Switch als zentraler Switch</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">-   Ethernet/ Fast Ethernet/ Gigabit Ethernet</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   mind. 16 x RJ45-Ports </span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   mind. 2 x SFP-Ports für SFP-Module</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   MRP-Unterstützung</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   VLANs</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Port-Trunking</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   19-Zoll-Montage</span>
                        </p>
                        <p />
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Betriebsspannung	: 1 x 230 V AC</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">vollständige Einbindung in das vorhandene Netzwerk als Austausch für vorhandene Switches</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">inkl. allem Zubehör wie Netzkabel und Konfigurationsspeicher</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="7110c304-572f-4903-b2b7-346dda17845a" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="f25ac693-422a-425a-9343-d52876dec17e" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Managebarer Switch als zentraler Switch</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053466" RNoPart="2">
                <RefPerfNo IDRef="GW_3053462" />
                <Qty>1.000</Qty>
                <QU>St</QU>
                <Description ID="c80310ad-8476-472e-9a06-288715d55e87">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Patchpanel 24 x RJ45, CAT 6A</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Anschluss mit LSA+Technik</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">-   Bauhöhe 1 HE</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Montage im bauseitigen Netzwerkschrank 19"-Rack, inkl. Klein- und Befestigungsmaterial</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="6dad8351-26fe-48fc-8c62-7cdb6799d952" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="9fb23bad-7cb9-4396-a2e4-c0e7d1ae71f3" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Patchpanel 24 x RJ45, CAT 6A</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <PerfDescr ID="GW_3053467">
                <PerfNo>11</PerfNo>
                <PerfLbl>Netzwerkparametrierung</PerfLbl>
                <Description ID="5774dc48-19db-4141-a2c2-1156f4dd0096">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Im Rahmen der Umstellung des PLS wird die Netzwerksegmentierung durch einen neuen managebaren Switch übernommen, über den mehrere VLANs realisiert werden.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">In den folgenden Positionen ist der gesamte Aufbau und die Parametrierung des Switches einschließlich Priorisierung, Einrichten von VLANs, Vergabe von IP-Adressen etc. für das Gesamtnetz einzukalkulieren.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die bauseits vorhandene Firewall ist in Abstimmung mit der IT-Abteilung des Auftraggebers zu aktualisieren und an die neu geschaffenen Bedingungen anzupassen.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="text-decoration:underline;background:#FFFFFF;">Netzwerkparametrierung</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </PerfDescr>
              <Item ID="GW_3053470" RNoPart="3">
                <RefPerfNo IDRef="GW_3053467" />
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="917f6c03-1daf-4cd6-9aff-3bc436235286">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Analyse und Anpassung vorhandene Netzwerktechnik</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Im Einzelnen ist eine Bestandsanalyse der vorhandenen Netzwerktechnik vorzunehmen, die aus folgenden Komponenten besteht:</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">-   1 x Switch</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   2 x PC-System</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   4 x E/A-Unterstation</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   1 x Firewall</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Nach der Bestandsanalyse sind ggf. neue Firmware-Versionen aufzuspielen und die Redundanzfunktionen des vorhandenen Netzwerks neu zu projektieren. Ebenso sind die bestehenden Leitungswege des Netzwerks in geringem Umfang anzupassen.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Analyse und Anpassung vorhandene Netzwerktechnik</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053469" RNoPart="4">
                <RefPerfNo IDRef="GW_3053467" />
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="83119e2c-05cf-470f-a53a-8d65f7006644">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Einrichtung neue Netzwerktechnik</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Einbringung des neuen Switches mit Anschluss an die Energieversorgung und netzwerktechnische Verbindung, inkl. Einrichtung der Redundanzfunktionen und ggf. Update auf aktuelle Firmware-Version.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Verdrahten neuer und bestehender Netzwerkleitungen an zu lieferndem Patchpanel.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Einrichtung neue Netzwerktechnik</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053471" RNoPart="5">
                <RefPerfNo IDRef="GW_3053467" />
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="808ea6cb-7a82-4770-946a-398936aa0e6c">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Einrichtung VLAN</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Einrichtung der VLANs (Anlagenbus, Terminalbus, DMZ) zur Funktion des angebotenen SCADA-Systems zur Anbindung von Prozessserver, NAS, Automatisierungsgerät und Firewall an zu liefernden Switch.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Einrichtung VLAN</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053472" RNoPart="6">
                <RefPerfNo IDRef="GW_3053467" />
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="4538dbb6-4a05-4099-a5a6-ebdc70399b67">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Abstimmung und Aktualisierung bauseitige Firewall</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Abstimmung mit dem Auftraggeber und anschließende Anpassung der bauseitigen Firewall hinsichtlich der durch die Maßnahme veränderten Bedingungen und entsprechend den Sicherheitsempfehlungen des Herstellers des angebotenen SCADA-Systems und den Anforderungen der verwendeten Software-Komponenten.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Es ist die größtmögliche für eine vollständige, sichere und schnelle Funktion erreichbare Sicherheit umzusetzen. Erstellen der Konfiguration und Einrichten der Log-Dateien auf der lokalen Festplatte eines Servers.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Einrichtung/ Anpassung der VPN-Router-Funktionalität zur Übertragung von Messwerten an einen Datenbankserver.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die Firewall-Regeln sind im Pflichtenheft zu beschreiben und abzustimmen.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Abstimmung und Aktualisierung bauseitige Firewall</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <PerfDescr ID="GW_3053473">
                <PerfNo>12</PerfNo>
                <PerfLbl>Schwenken der Netzwerkkabel</PerfLbl>
                <Description ID="b6e83770-c180-45ce-b6ca-252d7c9963c8">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Um den parallelen Betrieb des alten und neuen Leitsystems aufrecht erhalten zu können, sind provisorische Patchverbindungen zwischen dem alten und neuen Serverstandort durchzuführen. Erst nach Durchführung eines erfolgreichen Probebetriebs sind die internen und externen Netzwerkkabel Zug-um-Zug zurückzuziehen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Während des Probebetriebs kann es notwendig sein, zwischen dem bestehenden und dem neuen System umzuschwenken. Diese Arbeiten sind bei der Kalkulation zu berücksichtigen.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Schwenken der Netzwerkkabel</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </PerfDescr>
              <Item ID="GW_3053475" RNoPart="7">
                <RefPerfNo IDRef="GW_3053473" />
                <Qty>5.000</Qty>
                <QU>St</QU>
                <Description ID="55c03f50-fc6f-4753-95d8-8db9d514d0ab">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Erstellen von provisorischen Patchverbindungen</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Mit Hilfe der in den zu liefernden Patchkabelpaketen enthaltenen Patchkabel (LWL/Kupfer) herstellen einer Patchverbindung zwischen Patchpanel alt und Patchpanel neu bzw. Serverkomponenten für die Dauer der Inbetriebnahme bis zum Abschluss des Probebetriebs.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die Patchkabelverbindung ist beidseitig mit Angabe von Quelle und Ziel zu beschriften. Das zeitweise Herauspatchen während der Inbetriebnahme ist mit zu berücksichtigen.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Erstellen von provisorischen Patchverbindungen</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <PerfDescr ID="GW_3053476">
                <PerfNo>13</PerfNo>
                <PerfLbl>Verkabelung, Informationstechnik und Netzwerke</PerfLbl>
                <Description ID="597596a7-2a13-4ff2-a82a-1810707feba3">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Nachstehend aufgeführte Kabel und Leitungen liefern und betriebsfertig inklusive Kabelbeschriftungen verlegen. Die Kabelbeschriftung erfolgt entsprechend der Vorgaben des Auftraggebers. Die Verlegung soll in Doppelböden, Kabelrinnen, Steigetrassen, PVC-Kanälen oder Schutzrohren erfolgen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Das erforderliche Montagematerial wie Kabelbügelschellen, Kabelverschraubungen auch EMV etc. sowie das fachgerechte Öffnen und Schließen von Brandschotts ist im Einheitspreis zu berücksichtigen.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Verkabelung, Informationstechnik und Netzwerke</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </PerfDescr>
              <Item ID="GW_3053478" RNoPart="8">
                <RefPerfNo IDRef="GW_3053476" />
                <Qty>5.000</Qty>
                <QU>St</QU>
                <Description ID="a3ec17b8-85af-4e15-a892-69e6ff1e60f0">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Patchkabel RJ45, Länge 1,5 m, LAN CAT 6</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">farbige Ausführung, Stecker voll geschirmt mit Knickschutz</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Kabel UTP/BS 4 x 2 x AWG 26 mit gemeinsamer Abschirmung aus Aluminium-Folie und Cu-Geflecht.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Markenfabrikat mit Messprotokoll</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Patchkabel RJ45, Länge 1,5 m, LAN CAT 6</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053479" RNoPart="9">
                <RefPerfNo IDRef="GW_3053476" />
                <Qty>5.000</Qty>
                <QU>St</QU>
                <Description ID="3b8da286-1310-41ae-9a8d-a3e54c7a7ddd">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Patchkabel RJ45, Länge 3 m, LAN CAT 6</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">farbige Ausführung, Stecker voll geschirmt mit Knickschutz</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Kabel UTP/BS 4 x 2 x AWG 26 mit gemeinsamer Abschirmung aus Aluminium-Folie und Cu-Geflecht.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Markenfabrikat mit Messprotokoll</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Patchkabel RJ45, Länge 3 m, LAN CAT 6</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053480" RNoPart="10">
                <RefPerfNo IDRef="GW_3053476" />
                <Qty>5.000</Qty>
                <QU>St</QU>
                <Description ID="b3c4342b-8735-42bc-809a-44d9cd2058af">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Patchkabel RJ45, Länge 5 m, LAN CAT 6</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">farbige Ausführung, Stecker voll geschirmt mit Knickschutz</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Kabel UTP/BS 4 x 2 x AWG 26 mit gemeinsamer Abschirmung aus Aluminium-Folie und Cu-Geflecht.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Markenfabrikat mit Messprotokoll</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Patchkabel RJ45, Länge 5 m, LAN CAT 6</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Remark ID="GW_3263454">
                <Description ID="480943ea-1996-444b-b1e3-1f79b264d63d">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Netzwerksystemkabel</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Netzwerksystemkabel</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Remark>
              <Item ID="GW_3053502" RNoPart="11">
                <RefPerfNo IDRef="GW_3053476" />
                <Qty>200.000</Qty>
                <QU>m</QU>
                <Description ID="58faa35f-050e-4fe3-a75d-d3ea0810917e">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Netzwerksystemkabel LAN CAT 6A</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">UTP/BS 4 x 2 x AWG 24</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">4 Paare mit gemeinsamer Abschirmung aus Aluminium-Folie und CU-Geflecht, halogenfreie Ausführung, inkl. RJ45-Stecker mit Knickschutztülle</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">in Teillängen</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Netzwerksystemkabel LAN CAT 6A</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053503" RNoPart="12">
                <RefPerfNo IDRef="GW_3053476" />
                <Qty>20.000</Qty>
                <QU>St</QU>
                <Description ID="2e2cf1cf-9a49-43b6-9280-2eb168047de9">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Geschirmte Stecker RJ45, passend für v. g. LAN-Kabel</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Geschirmte Stecker RJ45, passend für v. g. LAN-Kabel</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053508" RNoPart="13">
                <Qty>20.000</Qty>
                <QU>St</QU>
                <Description ID="4f0ccfa9-7e0d-4839-8e6b-c827d100bb77">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Anschlüsse für Netzwerksystemkabel CAT 6A, RJ45-Stecker</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">inkl. abisolieren, in Anschlussdose bzw. Schrank einführen, zugentlasten und Kabelverschraubungen abdichten.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Anschlüsse für Netzwerksystemkabel CAT 6A, RJ45-Stecker</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
            </Itemlist>
          </BoQBody>
        </BoQCtgy>
        <BoQCtgy ID="GW_3053484" RNoPart="6">
          <LblTx>
            <p>
              <span style="background:#FFFFFF;">Energietechnische Verkabelung</span>
            </p>
          </LblTx>
          <NotApplBoQ>No</NotApplBoQ>
          <BoQBody>
            <Itemlist>
              <PerfDescr ID="GW_3053485">
                <PerfNo>14</PerfNo>
                <PerfLbl>Verkabelung</PerfLbl>
                <Description ID="c60a643c-6cac-40dc-b4d3-1c192536b6ed">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Nachstehend aufgeführte Kabel und Leitungen liefern und betriebsfertig verlegen einschließlich Befestigungsmaterial und ggf. KSV-Schellen bei Steigetrassen. Die Verlegung soll in Kabelrinnen, Steigetrassen, PVC-Kanälen, Schutzrohren und in Erde erfolgen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Anschlüsse werden nur an bauseitig beigestellten und vorhandenen Einrichtungen gesondert vergütet.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Verkabelung</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </PerfDescr>
              <Remark ID="GW_3053487">
                <Description ID="e7a7c8bd-c75d-458f-92e6-724b31a1d072">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Kunststoffkabel NYY-J</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Kunststoffkabel NYY-J</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Remark>
              <Item ID="GW_3053488" RNoPart="1">
                <RefPerfNo IDRef="GW_3053485" />
                <Qty>10.000</Qty>
                <QU>m</QU>
                <Description ID="61a0d300-877b-4fa5-b0dc-448aa5da5cd0">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Kunststoffkabel NYY-J 3 x 1,5 mm²</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">in Teillängen</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Kunststoffkabel NYY-J 3 x 1,5 mm²</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053489" RNoPart="2">
                <RefPerfNo IDRef="GW_3053485" />
                <Qty>10.000</Qty>
                <QU>m</QU>
                <Description ID="7416fdff-f434-47f6-94cc-93152110cd46">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Kunststoffkabel NYY-J 5 x 1,5 mm²</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">in Teillängen</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Kunststoffkabel NYY-J 5 x 1,5 mm²</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053490" RNoPart="3">
                <RefPerfNo IDRef="GW_3053485" />
                <Qty>10.000</Qty>
                <QU>m</QU>
                <Description ID="65d8c7fa-ee5c-4e70-856e-cb51b5ca07c3">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Kunststoffkabel NYY-J 5 x 2,5 mm²</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">in Teillängen</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Kunststoffkabel NYY-J 5 x 2,5 mm²</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Remark ID="GW_3053493">
                <Description ID="7a825f19-0307-430e-9315-b488dd7a3ab4">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Ölflex-Kabel</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="text-decoration:underline;background:#FFFFFF;">Ölflex-Kabel</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Remark>
              <Item ID="GW_3053494" RNoPart="4">
                <RefPerfNo IDRef="GW_3053485" />
                <Qty>5.000</Qty>
                <QU>m</QU>
                <Description ID="fd2c5fd8-6695-45e6-b46e-1231d84592fc">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Ölflex-Robust-Nummernkabel 3 x 1,5 mm²</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">in Teillängen</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Ölflex-Robust-Nummernkabel 3 x 1,5 mm²</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053497" RNoPart="5">
                <RefPerfNo IDRef="GW_3053485" />
                <Qty>5.000</Qty>
                <QU>m</QU>
                <Description ID="bff0bddb-d410-4080-97b4-d93405473256">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Ölflex-Robust-Nummernkabel 5 x 1,5 mm²</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">in Teillängen</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Ölflex-Robust-Nummernkabel 5 x 1,5 mm²</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053498" RNoPart="6">
                <RefPerfNo IDRef="GW_3053485" />
                <Qty>5.000</Qty>
                <QU>m</QU>
                <Description ID="89b5ad8b-06eb-4318-92fb-bcb701edb813">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Ölflex-Robust-Nummernkabel 5 x 2,5 mm²</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">in Teillängen</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Ölflex-Robust-Nummernkabel 5 x 2,5 mm²</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <PerfDescr ID="GW_3053504">
                <PerfNo>15</PerfNo>
                <PerfLbl>Kabel- und Leitungsanschlüsse</PerfLbl>
                <Description ID="5d3cd7f7-69cb-44d3-98a8-84d46e754355">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Nachstehende Anschlüsse von Kabeln und Leitungen an bauseitigen Aggregaten, wie Motoren, Unterverteilern, Bedienungs- und Messgeräten, inkl. abisolieren, in Anschlussdose bzw. Schrank einführen, entsprechend dem jeweiligen Querschnitt und Kabeltyp mit Kabelschuhen anschließen, zugentlasten und Kabelverschraubungen abdichten.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Anschlüsse an Lieferteilen des Auftragnehmers sind in die Einheitspreise einzukalkulieren.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="text-decoration:underline;background:#FFFFFF;">Kabel- und Leitungsanschlüsse</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </PerfDescr>
              <Item ID="GW_3053506" RNoPart="7">
                <RefPerfNo IDRef="GW_3053504" />
                <Qty>5.000</Qty>
                <QU>St</QU>
                <Description ID="56626aff-e817-4991-8c07-95455e0e4a01">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Anschlüsse für NYY, NYM und Ölflex 3 x 1 mm² bis 5 x 2,5 mm²</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Anschlüsse für NYY, NYM und Ölflex 3 x 1 mm² bis 5 x 2,5 mm²</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
            </Itemlist>
          </BoQBody>
        </BoQCtgy>
        <BoQCtgy ID="GW_3053513" RNoPart="7">
          <LblTx>
            <p>
              <span style="background:#FFFFFF;">Automatisierungstechnik</span>
            </p>
          </LblTx>
          <NotApplBoQ>No</NotApplBoQ>
          <BoQBody>
            <Itemlist>
              <PerfDescr ID="GW_3263455">
                <PerfNo>16</PerfNo>
                <PerfLbl>Automatisierungstechnik</PerfLbl>
                <Description ID="508cba66-b99e-4f3d-933a-7ed257e1d9be">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Die alte Software-SPS InControl, die über Interbus S mit vier E/A-Unterstationen verbunden ist, wird durch eine Siemens Simatic S7-1500 ersetzt.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Zum Funktionserhalt muss zunächst eine Analyse der derzeitigen Automatisierungstechnik durchgeführt werden. Anschließend ist durch den Auftragnehmer auf Grundlage der Analyse und in Absprache mit dem Auftraggeber eine Funktionsbeschreibung zu erstellen. Das neue Automatisierungsgerät wird in einem bauseits vorhandenen Schaltschrank installiert und über Industrial Ethernet mit dem zentralen Switch verbunden. Über Profinet werden die zu installierenden dezentralen Peripheriebaugruppen vom Typ SIMATIC ET 200MP angebunden, die ebenfalls in weiteren bauseits vorhandenen Schaltschränken zu installieren sind.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">An das Automatisierungsgerät und die dezentrale Peripheriebaugruppen sind mittels Analog- und Digitalbaugruppen die Signale der Sensoren und Aktoren im Feld anzubinden.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Zum parallelen Aufbau und schnellem Umschwenken der Signale aus dem Feld zwischen der alten und neuen Automatisierungstechnik werden die Signale auf Übergabemodule verdrahtet und die Steuerungen mit Frontadaptern ausgestattet.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die Projektierung des neuen Automatisierungsgerätes erfolgt auf Grundlage der Bestandsanalyse, einer zur Verfügung gestellten Funktionsbeschreibung und in Abstimmung mit dem Auftraggeber.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Nach einem erfolgreichen 4-wöchigen Probebetrieb ist der Rückbau der alten Automatisierungstechnik vorzusehen.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Automatisierungstechnik</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </PerfDescr>
              <Item ID="GW_3053514" RNoPart="1">
                <RefPerfNo IDRef="GW_3263455" />
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="b3e2b9b4-6813-4496-935c-79de0f973a58">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Analyse Bestandsautomatisierung</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Zur umfassenden Analyse der vorhandenen Automatisierungsstruktur werden im Wesentlichen folgende Leistungen notwendig:</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Analyse der vorhandenen Automatisierungsprogramme des Automatisierungsgerätes inkl. aller unterlagerten Automatisierungsgeräte mit Programmiergeräten und Software des Anbieters. Bauseitige Leistungen werden nicht durchgeführt.</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Analyse der vorhandenen Busstruktur.</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Analyse der Kommunikation mit Angabe der Kommunikationspartner und der gekoppelten Signale in tabellarischer Form.</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Analyse der ausgelesenen Kommunikationsstrukturen/ -bausteine der Automatisierungssysteme.</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Analyse der Signale zur Übertragung zum Leitsystem.</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Verbale Beschreibung mit grafischer Darstellung der Regelschemata mit AKZ-Bezeichnung der Aggregate, Steuerungsabläufen, Verriegelungen, Anlagenschutzeinrichtungen, Plausibilitätsprüfungen etc. Sollte eine Analyse von einzelnen Programmteilen nicht möglich sein, so ist in Abstimmung mit der Bauleitung ein Warmtest vor Ort durchzuführen.</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Analyse der gesamten Ein- und Ausgabeebene des Automatisierungsgerätes; hierzu zählen sowohl das Zentralgerät als auch vorhandene Erweiterungsgeräte und dezentrale Peripherie, die über Profibus, Profinet oder digitale E/A angeschlossen sind.</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Abgleich zwischen Analyseergebnis und der bauseits beigestellten Funktionsbeschreibung auf Abweichungen und Darstellung der Unterschiede in grafischer, tabellarischer und textlicher Form.</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Alle Leistungen, die zu einer Neuerstellung von Automatisierungsprogrammen unter Beibehaltung der Funktion sowie eingestellten Sollwerten und Parametern notwendig sind; Funktionen sind transparent zu erarbeiten und darzustellen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die unterlagerten Strukturen sind dem Bestandskonfigurator zu entnehmen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Datenumfang am zu modernisierenden Automatisierungsgerät inkl. E/A-Unterstationen:</span>
                        </p>
                        <p />
                        <p style="tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">digitale Signale		: bis ca. 344 Stück</span>
                        </p>
                        <p style="tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">analoge Signale		: bis ca. 36 Stück</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Als Pauschalfestpreis.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Analyse Bestandsautomatisierung</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3789922" RNoPart="2">
                <RefPerfNo IDRef="GW_3263455" />
                <Qty>1.000</Qty>
                <QU>St</QU>
                <Description ID="eb56653a-57e5-4fe5-a574-5a7ed13af26d">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">CPU SIMATIC S7-1500</span>
                        </p>
                        <p />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Arbeitsspeicher für Programm	: 500 kByte</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Arbeitsspeicher für Daten	: 3 MByte</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Ladespeicher		: Memory Card 2 GB</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Peripherieadressbereich	: 32 kByte E/A-Daten</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Spannungsversorgung		: 24 V DC</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Stromaufnahme		: 0,85 A</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Einschaltstrom		: 2,4 A</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Busschnittstellen		: 2 x ProfiNet, RJ45, 100 Mbit/s</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">Protokolle			: IP v4, ProfiNet I/O-Controller, I/O-Device</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">			: offene IE-Kommunikation, MRP-Automanager</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">inkl. Memory Card, Profilschiene, Programmierung über Step 7 im TIA-Portal</span>
                        </p>
                        <p />
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Hersteller	: Siemens</span>
                        </p>
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Typ	: CPU 1515-2 PN</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">oder gleichwertig</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="888145db-09e5-4b4e-989c-8c6bd541519f" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="bcf753b9-18d7-4863-96bf-ed26aaf6c752" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">CPU SIMATIC S7-1500</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053521" RNoPart="3">
                <RefPerfNo IDRef="GW_3263455" />
                <Qty>1.000</Qty>
                <QU>St</QU>
                <Description ID="ce8bec4d-32c7-41a4-b2a8-da2c5780b7eb">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Kommunikationsmodul CP Industrial Ethernet</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">für die Schienenmontage</span>
                        </p>
                        <p />
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Hersteller	: Siemens</span>
                        </p>
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Typ	: CP 1545-1</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">oder gleichwertig</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="655cd201-1ed8-42a2-b4ea-766cc67eb3a4" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="67bc968b-cf9a-49ae-afe6-8f6198b5f304" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Kommunikationsmodul CP Industrial Ethernet</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053528" RNoPart="4">
                <RefPerfNo IDRef="GW_3263455" />
                <Qty>3.000</Qty>
                <QU>St</QU>
                <Description ID="fc12b4c6-ab7c-4b8e-8cef-e0a1e04767bf">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Dezentrale Peripheriebaugruppe ET 200MP</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">für den Anschluss bis zu 12 E/A-Baugruppen über Profinet, 0,25 ms </span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">taktsynchroner Betrieb Hot SWAP, inklusive Servermodul und Busadapter 2 x RJ45</span>
                        </p>
                        <p />
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Hersteller	: Siemens</span>
                        </p>
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Typ	: IM 155-5PN High Feature, 6ES7155...</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">mit komplettem Zubehör</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Dezentrale Peripheriebaugruppe ET 200MP</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3090632" RNoPart="5">
                <RefPerfNo IDRef="GW_3263455" />
                <Qty>2.000</Qty>
                <QU>St</QU>
                <Description ID="fab06382-8779-4abe-b040-e167106f7c08">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Digitalbaugruppe DI 16</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">24 V DC, High Feature, 16 Eingänge, Status-LED, Potenzialtrennung,</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">inkl. Push-In-Frontstecker</span>
                        </p>
                        <p />
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Hersteller	: Siemens</span>
                        </p>
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Typ	: 6ES7521-1BH00-0AB0</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">oder gleichwertig</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="2afc48cd-b4c6-4fc8-ad20-0ce7937bd88d" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="8155d2a7-2236-4080-ab4c-a712a5183e62" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Digitalbaugruppe DI 16</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053523" RNoPart="6">
                <RefPerfNo IDRef="GW_3263455" />
                <Qty>5.000</Qty>
                <QU>St</QU>
                <Description ID="0c8378df-88c9-40c1-be58-334ec6d1d812">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Digitalbaugruppe DI 32</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">24 V DC, High Feature, 32 Eingänge, Status-LED, Potenzialtrennung,</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">inkl. Push-In-Frontstecker</span>
                        </p>
                        <p />
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Hersteller	: Siemens</span>
                        </p>
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Typ	: 6ES7521-1BL00-0AB0</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">oder gleichwertig</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="f3450af2-5276-4815-b572-9daae5d454d1" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="4ecd6852-c7c9-4db7-bb22-6f4937532d80" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Digitalbaugruppe DI 32</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3090631" RNoPart="7">
                <RefPerfNo IDRef="GW_3263455" />
                <Qty>1.000</Qty>
                <QU>St</QU>
                <Description ID="65aece3c-4e7e-4d5a-b2e7-3f6e93559e51">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Digitalbaugruppe DQ 8</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">24 V DC, High Feature, 8 Ausgänge, Status-LED, Potenzialtrennung,</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">inkl. Push-In-Frontstecker</span>
                        </p>
                        <p />
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Hersteller	: Siemens</span>
                        </p>
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Typ	: 6ES7522-1BF00-0AB0</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">oder gleichwertig</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="1149c3fa-b85d-4656-a01f-19d914835a99" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="9676655f-a3cf-4d80-a66d-a4fea6228501" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Digitalbaugruppe DQ 8</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053522" RNoPart="8">
                <RefPerfNo IDRef="GW_3263455" />
                <Qty>4.000</Qty>
                <QU>St</QU>
                <Description ID="1f066d9f-47e8-4d95-b005-cc0db72b4945">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Digitalbaugruppe DQ 32</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">24 V DC, High Feature, 32 Ausgänge, Status-LED, Potenzialtrennung,</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">inkl. Push-In-Frontstecker</span>
                        </p>
                        <p />
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Hersteller	: Siemens</span>
                        </p>
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Typ	: 6ES7522-1BL01-0AB0</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">oder gleichwertig</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="7aca4e74-e7f0-499a-9d86-27ae81860b75" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="9dc53cb9-d6f8-4c54-bc8b-1674f93141ea" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Digitalbaugruppe DQ 32</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053525" RNoPart="9">
                <RefPerfNo IDRef="GW_3263455" />
                <Qty>6.000</Qty>
                <QU>St</QU>
                <Description ID="79afa03f-2e3a-4f52-9144-3ecb2a94b403">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Analogbaugruppe AI 8</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Standard mit 8 analogen Signalen 0/4 - 20 mA, Zweileiteranschluss, 16 Bit, Potenzialtrennung intern/ extern, inkl. Push-In-Frontstecker</span>
                        </p>
                        <p />
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Hersteller	: Siemens</span>
                        </p>
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Typ	: 6ES7531-7KF00-0AB0</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">oder gleichwertig</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="aaab0fc1-0caf-4596-aa24-fe6ab98ec76a" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="2cdd1d58-7a18-464d-99df-32e4c7b23d6f" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Analogbaugruppe AI 8</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053524" RNoPart="10">
                <RefPerfNo IDRef="GW_3263455" />
                <Qty>1.000</Qty>
                <QU>St</QU>
                <Description ID="c95d4045-37ab-4725-94fd-0ffd80474276">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Analogbaugruppe AQ 8</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Standard mit 8 analogen Signalen, Zweileiteranschluss, 16 Bit, inkl. Push-In-Frontstecker</span>
                        </p>
                        <p />
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Hersteller	: Siemens</span>
                        </p>
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Typ	: 6ES7532-5HF00-0AB0</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">oder gleichwertig</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="5b7addb2-60cf-493a-b325-ad55f96de035" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="fc7f6b49-ec5c-4fe4-9cd5-cb46cbd031c7" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Analogbaugruppe AQ 8</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3789923" RNoPart="11">
                <RefPerfNo IDRef="GW_3263455" />
                <Qty>4.000</Qty>
                <QU>St</QU>
                <Description ID="ea1fe703-a768-4f4b-be3c-f06dade6421d">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Laststromversorgung für SIMATIC S7-1500/ ET 200MP</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">für die Schienenmontage</span>
                        </p>
                        <p />
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Eingang	: 120/ 230 V AC</span>
                        </p>
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Ausgang	: 24 V DC, 70 W</span>
                        </p>
                        <p />
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Hersteller	: Siemens</span>
                        </p>
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Typ	: PM 70 W 120/230 VAC</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">oder gleichwertig</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="a2f7bcd1-bf12-4963-9592-a7317068549d" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="e453bdd5-91ad-4bff-b7be-122d45076be0" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Laststromversorgung für SIMATIC S7-1500/ ET 200MP</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3789924" RNoPart="12">
                <RefPerfNo IDRef="GW_3263455" />
                <Qty>4.000</Qty>
                <QU>St</QU>
                <Description ID="2a539437-9e29-480b-8428-dd672df2a333">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Installationszubehör SIMATIC S7-1500/ ET 200MP</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">wie Profilschiene/ Modulträger, Beschriftungsbögen, Kleinmaterial, usw., das zur funktionsbereiten und fachgerechten Installation einer SIMATIC S7-1500 oder ET 200MP in einem Schaltschrank notwendig ist.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Installationszubehör SIMATIC S7-1500/ ET 200MP</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053518" RNoPart="13">
                <RefPerfNo IDRef="GW_3263455" />
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="1031f189-f245-456f-955c-eb9b26736b36">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Zulage zur Montage der Automatisierungstechnik in bauseitigen Schrank</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Montage einer zu liefernden Automatisierungskomponente einschließlich E/A-Modulen, elektronischem Sicherungsautomaten in einer bauseitigen Schaltschränken.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Montage auf vorhandener Montageplatte einschließlich Befestigungsmaterial und Anschluss an vorhandene 24-V-DC-Versorgung einschließlich Verdrahtungsmaterial, Anpassen der Dokumentation.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Zulage Montage der Automatisierungstechnik</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3789944" RNoPart="14">
                <RefPerfNo IDRef="GW_3263455" />
                <Qty>1.000</Qty>
                <QU>St</QU>
                <Description ID="434311ba-6a4f-4130-8abd-1e7acb8bbd89">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Funktionsbeschreibung Automatisierungsgerät</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Erstellung einer Funktionsbeschreibung zur Beschreibung der Funktionen des Automatisierungsgeräts anhand der Hard- und Softwareanalyse.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Erstellung in enger Abstimmung mit dem Betriebspersonal.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Inkl. der Darstellung von Schrittkettendarstellungen zur Verdeutlichung der Funktionsabläufe. Berücksichtigung der E/A-Listen der elektrotechnischen Konfiguration und Klärung fehlender Informationen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Vorlage beim Auftraggeber und bis zu 3-malige Anpassung bei Änderungswünschen (Fehler sind stets zu korrigieren und werden nicht gezählt).</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">als Pauschalfestpreis</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Funktionsbeschreibung Automatisierungsgerät</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053515" RNoPart="15">
                <RefPerfNo IDRef="GW_3263455" />
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="11a26748-5c19-420b-be37-715d87fa9cea">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Automatisierungsprogramm</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">mit den unterlagerten Steuerungen/Systemen (z. B. ET 200MP).</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die zwei Onboard-Profinet-Schnittstellen der Automatisierungsgeräte sind ausschließlich für den Aufbau der unterlagerten Profinet I/O-Netzwerke zu nutzen. Eine Mischung mit weiteren Protokollen wie z. B. einer S7-Kommunikation soll über diese Schnittstellen nicht erfolgen. Für den Anlagenbus und die S7-Kommunikation sind jeweils separate Kommunikationsprozessoren vorzusehen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Grundlage für die Erstellung der einzelnen Anwenderprogramme sind:</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">-   Funktionsbeschreibung</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Ergebnis der Analyse der vorhandenen Automatisierungsstruktur</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   abgestimmtes Deltadokument</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   abgestimmtes Pflichtenheft</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Erstellung, Lieferung und Inbetriebnahme des Automatisierungsprogramms inkl. Test und Optimierung des Anwenderprogramms im Rahmen des 4-wöchigen Probebetriebs.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Im Wesentlichen werden folgende Leistungen notwendig:</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Konfiguration der Hardware</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Engineering von Messstellen, Aggregaten usw.</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Anwenderprogramm auf Grundlage der Funktionsbeschreibung, der Verfahrensdarstellung, der Analysenergebnisse, des genehmigten Pflichtenheftes</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   erstellen der Kommunikationsverbindungen über den Anlagenbus Industrial Ethernet, Profinet etc. zum Leitsystem, dezentraler Peripherie usw.</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Empfang von Befehlen und Soll- sowie Istwerten vom Leitsystem</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Aufbereitung und zeitfolgerichtige Übertragung von Digital- und Analogwerten sowie Statusmeldungen</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   anlegen von Datenbausteinen für den Austausch mit den Softwarekomponenten der Leittechnik</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   erstellen der Kommunikationsverbindungen über den Feldbus Profinet zu den dezentralen Peripheriebaugruppen (ET 200MP-Reihe) sowie weiteren Teilnehmern</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Zuordnung zu Alarmklassen und Eintragungen der Meldetexte</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Eintragung der PV-Nummern, Anlagenkennzeichen und Klartexte</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Einrichtung einer Meldeschwallunterdrückung</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   vollständige, für dritte nachvollziehbare Kommentierung des Programmcodes</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Einrichtung der Messbereiche und Grenzwerte für Analogwerte.</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   anlegen von erforderlichen internen Variablen.</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   einrichten des Tag- und Alarmlogging.</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   vollständiger Datenpunkttest als Eigenüberprüfung und mit Einbindung des Auftraggebers; von beiden Seiten unterschrieben und als Teil der Dokumentation zu übergeben</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Sowie sämtliche, auch im Vortext genannten Aufgabenstellungen, die zu einer funktionsfähigen Anlage notwendig sind.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Inbetriebnahme des Programms in Zusammenarbeit mit dem Betriebspersonal und der Bauüberwachung.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Umsetzung auf neuem Automatisierungssystem bestehend aus S7-1500.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Datenumfang inkl. Unterlagerter ET 200MP:</span>
                        </p>
                        <p />
                        <p style="tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">digitale Signale		: bis ca. 344 Stück</span>
                        </p>
                        <p style="tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">analoge Signale		: bis ca. 36 Stück</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Programm liefern, implementieren und in Betrieb nehmen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Als Pauschalfestpreis.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Automatisierungsprogramm</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <PerfDescr ID="GW_3789925">
                <PerfNo>17</PerfNo>
                <PerfLbl>Umschaltung zwischen Bestand und Neubau</PerfLbl>
                <Description ID="db97f681-ac1c-48be-9bd4-1ff3397f3676">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Um einen weitestgehend unterbrechungsfreien Betrieb beim Umbau gewährleisten zu können, muss eine vorherige Anpassung erfolgen. Die Signalverbindungen der bisherigen Steuerung und den Unterstationen werden dafür zunächst auf Übergabemodule umverdrahtet. Über Systemkabel kann nun die Feldebene schnell und unkompliziert entweder mit der bestehenden Steuerung oder mit dem neuen, parallel aufgebauten Automatisierungsgerät verbunden werden. Bei beiden Steuerungen werden dafür Systemkabel mit offenen Enden installiert.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Umschaltung zwischen Bestand und Neubau</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </PerfDescr>
              <Item ID="GW_3789932" RNoPart="16">
                <RefPerfNo IDRef="GW_3789925" />
                <Qty>12.000</Qty>
                <QU>St</QU>
                <Description ID="646f520f-3168-4f11-9884-34a2a0df4dbd">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Übergabemodul 14-polig</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Übergabemodul, Push-in-Anschluss, Flachbandkabel-Steckverbinder</span>
                        </p>
                        <p />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Nennspannung U</span>
                          <span style="font-size:8pt;vertical-align:sub;background:#FFFFFF;">N</span>
                          <span style="background:#FFFFFF;">		: UN 60 V AC/DC</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm;">
                          <span style="background:#FFFFFF;">max. Strombelastbarkeit je Zweig	: 1 A</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">Polzahl			: 14</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Normen/Bestimmungen	: IEC 60664, DIN EN 50178, IEC 62103</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Hersteller	: Phoenix Contact</span>
                        </p>
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Typ	: VIP-2/PT/FLK14</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">oder gleichwertig</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="dfbecdc5-b76a-4772-89e1-85452eb93c91" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="59e46f1c-f663-4c95-b865-8c6f18398268" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Übergabemodul 14-polig</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3789933" RNoPart="17">
                <RefPerfNo IDRef="GW_3789925" />
                <Qty>9.000</Qty>
                <QU>St</QU>
                <Description ID="b839d87b-d340-4967-a472-61d8c3e2638b">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Übergabemodul 50-polig</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Übergabemodul, Push-in-Anschluss, Flachbandkabel-Steckverbinder</span>
                        </p>
                        <p />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Nennspannung U</span>
                          <span style="font-size:8pt;vertical-align:sub;background:#FFFFFF;">N</span>
                          <span style="background:#FFFFFF;">		: UN 60 V AC/DC</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm;">
                          <span style="background:#FFFFFF;">max. Strombelastbarkeit je Zweig	: 1 A</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">Polzahl			: 50</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Normen/Bestimmungen	: IEC 60664, DIN EN 50178, IEC 62103</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Hersteller	: Phoenix Contact</span>
                        </p>
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Typ	: VIP-3/PT/FLK50</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">oder gleichwertig</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="bfd1a144-df31-4d7f-915f-94bb5c8a0d1a" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="486290bd-a0bf-4e6f-b58c-a8354a51eb3f" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Übergabemodul 50-polig</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3266767" RNoPart="18">
                <RefPerfNo IDRef="GW_3789925" />
                <Qty>24.000</Qty>
                <QU>St</QU>
                <Description ID="ca3eebb5-9b18-48c5-b888-d24e63e7cbe4">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Systemkabel geschirmt mit einem offenen Ende 14-polig, bis 3 m</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">konfektioniertes, geschirmtes Rundkabel;</span>
                        </p>
                        <p />
                        <p style="tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Anschluss 1		: Einzeladern (14-polig)</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">(Die Adern sind beschriftet und mit Aderendhülsen versehen)</span>
                        </p>
                        <p />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Anschluss 2		: 14-polige Federleiste für System Phoenix-Contact FLKM 14, Varioface-Modul</span>
                        </p>
                        <p />
                        <p style="tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Nennspannung UN		: 125 V AC/DC</span>
                        </p>
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Steckverbinder Modulseite	: Federleiste</span>
                        </p>
                        <p style="tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Polzahl Modulseite		: 14</span>
                        </p>
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Steckverbinder Steuerungsseite	: Einzeladern</span>
                        </p>
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Polzahl Steuerungsseite	: 14</span>
                        </p>
                        <p style="tab-stops:5mm 25mm;">
                          <span style="background:#FFFFFF;">Kabellänge fix		: bis 3 m</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Systemkabel geschirmt mit einem offenen Ende 14-polig, bis 3 m</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3266766" RNoPart="19">
                <RefPerfNo IDRef="GW_3789925" />
                <Qty>18.000</Qty>
                <QU>St</QU>
                <Description ID="b81f2545-6030-4667-8100-2b2c1d640976">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Systemkabel geschirmt mit einem offenen Ende 50-polig, bis 3 m</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">konfektioniertes, geschirmtes Rundkabel;</span>
                        </p>
                        <p />
                        <p style="tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Anschluss 1		: Einzeladern (50-polig)</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">(Die Adern sind beschriftet und mit Aderendhülsen versehen)</span>
                        </p>
                        <p />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Anschluss 2		: 50-polige Federleiste für System Phoenix-Contact FLKM 50, Varioface-Modul</span>
                        </p>
                        <p />
                        <p style="tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Nennspannung UN		: 125 V AC/DC</span>
                        </p>
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Steckverbinder Modulseite	: Federleiste</span>
                        </p>
                        <p style="tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Polzahl Modulseite		: 50</span>
                        </p>
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Steckverbinder Steuerungsseite	: Einzeladern</span>
                        </p>
                        <p style="tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Polzahl Steuerungsseite	: 50</span>
                        </p>
                        <p style="tab-stops:5mm 25mm;">
                          <span style="background:#FFFFFF;">Kabellänge fix		: bis 3 m</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Systemkabel geschirmt mit einem offenen Ende 50-polig, bis 3 m</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3266769" RNoPart="20">
                <RefPerfNo IDRef="GW_3789925" />
                <Qty>344.000</Qty>
                <QU>St</QU>
                <Description ID="595048eb-242c-4e3e-8da1-9f08017a9d1c">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Umverdrahtung von binären Ein- und Ausgängen auf Übergabemodul</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Für Signale, die über Adapterstecker mit den neuen Baugruppen verbunden werden.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Verdrahtung für einen Ein- oder Ausgang mit 2-Leiter-Anschluss als flexible Einzelader bis ca. 2,5 m Länge mit 0,75 mm² Querschnitt unterschiedlicher Farben nach Angabe der Bauleitung zwischen vorhandenen Übergabeklemmen bzw. Schaltgerät und E/A-Interface liefern, verlegen in vorhandenen Verdrahtungskanälen und zunächst paralleles Anschließen mit Aderendhülsen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Nach Inbetriebnahme der neuen AS-/AG-Demontage der Verdrahtung zur früheren E/A-Ebene und endgültigem Anschluss der neuen Signalverdrahtung. </span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Einschließlich Öffnen und Schließen der vorhandenen Verdrahtungskanäle und Entsorgung von altem Verdrahtungsmaterial.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Umverdrahtung von binären Ein- und Ausgängen auf Übergabemodul</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3266770" RNoPart="21">
                <RefPerfNo IDRef="GW_3789925" />
                <Qty>36.000</Qty>
                <QU>St</QU>
                <Description ID="8cd7fbdb-2566-4d15-ad15-8b486d59a64d">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Umverdrahtung von analogen Ein- und Ausgängen auf Übergabemodul, jedoch zunächst provisorisches Einschleifen der Stromsignale und Freiklemmen vorhandener E/A-Karten. Nach Abschluss der Inbetriebnahme endgültiger Anschluss und Verlegung der Signalleitungen. Einschließlich aller erforderlichen Zwischenklemmen für den provisorischen Betrieb. </span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Umverdrahtung von analogen Ein- und Ausgängen auf Übergabemodul</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
            </Itemlist>
          </BoQBody>
        </BoQCtgy>
        <BoQCtgy ID="GW_3053529" RNoPart="8">
          <LblTx>
            <p>
              <span style="background:#FFFFFF;">Messtechnik</span>
            </p>
          </LblTx>
          <NotApplBoQ>No</NotApplBoQ>
          <BoQBody>
            <Itemlist>
              <PerfDescr ID="GW_3263457">
                <PerfNo>18</PerfNo>
                <PerfLbl>Messtechnik</PerfLbl>
                <Description ID="e80ee9e9-3830-4895-b28d-31f5f2097e1a">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Im Bereich der Messtechnik ist die kontinuierliche Messung der zwei Messwasserleitungen 23 und 4 zu erneuern und dabei die bisher getrennte Trübungsmessung mittels neuer Sensoren zu integrieren.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die neuen Sensoren je Messleitung für pH-Wert, elektrische Leitfähigkeit, Temperatur, Sauerstoff und Trübung werden in einem Durchflussmesstopf installiert und mit einem gemeinsamen Multiparameter-Messumformer verbunden. Der Messumformer wertet die Signale aus und stellt sie dem PLS zur Verfügung. Hierfür sind alle Verdrahtungsarbeiten in den Einzelpositionen zu berücksichtigen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Ansteuerbare Ventile im Aufbau der kontinuierlichen Messung dienen der Durchflusssteuerung und sind ebenfalls zu verbauen. Als weiteres Material sind Rohrelemente, Verschraubungen, Dichtungen und zusätzliches Installations- und Kleinmaterial zu verstehen, die zu einem fachgerechten Einbau der Messtechnik nötig sind. </span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Um eine größere Betriebsunterbrechung zu vermeiden, wird die neue Messtechnik provisorisch parallel zum Bestand aufgebaut. Nach einem erfolgreichen Probebetrieb wird der Bestand zurückgebaut und die neue Messtechnik an ihrem endgültigen Standort montiert.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Messtechnik</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </PerfDescr>
              <Item ID="GW_3262580" RNoPart="1">
                <RefPerfNo IDRef="GW_3263457" />
                <Qty>2.000</Qty>
                <QU>St</QU>
                <Description ID="e2548aef-666f-4ccc-83e9-7e15ef9810f5">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Multiparameter-Messumformer</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Ausführung gemäß der in Merkblatt DWA-M 256 festgelegten Mindestanforderungen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Multiparameter-Messumformer für den Anschluss von mind. 6 Sensoren entsprechend der Anforderungen der Maßnahme.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Bestehend aus Terminal/ Controller, Versorgungsmodul und einem Controller-Modul mit Ethernetschnittstelle zur Anbindung an Profinet zu Messwertübertragung an das angebotene SCADA-System.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Ausgestattet mit folgenden Eigenschaften:</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Bedieneinheit mit mind. 4 Tasten</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   mit USB-Schnittstelle</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Eingangsspannung mind. 220 - 240 V AC, 50/60 Hz</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   freie Zuordnung der Sensoren zu den Ausgängen</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   programmierbare potenzialfreie Relaiskontakte</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   mit hintergrundbeleuchtetem, grafischem Display</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   mit integrierter Backup-Controller-Funktion für erhöhte Betriebssicherheit</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   mit integriertem Datenlogger für 525 600 Datensätze</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   hohe EMV-Störfestigkeit</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   integrierter Überspannungsschutz</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Fehlerverhalten laut Namur NE43</span>
                        </p>
                        <p />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Messparameter		: pH-/Redox, Sauerstoff, Leitfähigkeit, Temperatur, Trübung, Feststoff, Ammonium, Nitrat, Kohlenstoff (CSB, TOC, DOC, BSB, SAK) in beliebiger Zusammenstellung</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Geräteschutz		: Schutzart IP 66</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="88f157b1-530d-4215-8d93-c993cd1caa34" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="76f98023-3399-4d96-8b22-c210385d73f9" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Multiparameter-Messumformer</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3262582" RNoPart="2">
                <RefPerfNo IDRef="GW_3263457" />
                <Qty>2.000</Qty>
                <QU>St</QU>
                <Description ID="a47be5f6-9a46-4aae-8b39-6ee9a2cc0f3d">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Sensor pH-Wert</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">pH/Redox Messwertgeber inklusive pH-Messkette und Sensor-Anschlusskabel im SET, passend zu oberhalb angebotenem Messumformer.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Ausführung gemäß der in Merkblatt DWA-M 256 festgelegten Mindestanforderungen für Messgeräte.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Ausgestattet mit folgenden Eigenschaften:</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   integrierter Blitzschutz</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Messwertgeber mit integriertem Vorverstärker zur niederohmigen Signalübertragung</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Sensorüberwachungs-Funktion</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Thermistorsystem zur Temperaturkompensation</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   mit Schraub-/ Steckverbindung zum Anschluss des Sensoranschlusskabels</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   pH-Messkette mit Festelektrolyt für stark belastete Proben</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   IP 68</span>
                        </p>
                        <p />
                        <p style="tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Messbereich		: 2 bis12 pH </span>
                        </p>
                        <p />
                        <p style="tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">Anschluss			: wasserdichter Steckkopf</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">inkl. Standard-Anschlusskabel, mind. 2 m</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">inkl. Zusatzmaterial zum Einbau in angebotenem Messtopf</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="6d86e2d3-6677-432c-a944-1f634652906b" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="91dc6760-3ac1-4b6b-ba10-b835635538a7" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Sensor pH-Wert</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3262583" RNoPart="3">
                <RefPerfNo IDRef="GW_3263457" />
                <Qty>2.000</Qty>
                <QU>St</QU>
                <Description ID="713fce27-3637-46ab-bbcf-a99b757226f2">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Sensor el. Leitfähigkeit/ Temperatur</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Ausführung gemäß der in Merkblatt DWA-M 256 festgelegten Mindestanforderungen für Messgeräte.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Digitaler Leitfähigkeits-Messwertgeber zum Anschluss an den oberhalb angebotenen Multiparameter-Messumformer; mit integriertem Temperatursensor.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Ausgestattet mit folgenden Eigenschaften:</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   4 Elektroden-Leitfähigkeitsmesszelle</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Thermistorsystem zur Temperaturkompensation</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   abriebfeste Carbon-Elektroden</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   mit Schraub-/ Steckverbindung zum Anschluss des Sensoranschlusskabels</span>
                        </p>
                        <p />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Messbereich		: 10 uS/cm bis 500 mS/cm</span>
                          <br />
                          <span style="background:#FFFFFF;">0 bis 70 Salinität</span>
                          <br />
                          <span style="background:#FFFFFF;">0 bis 2000 mg/l TDS</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="text-indent:-177pt;margin-left:177pt;">
                          <span style="background:#FFFFFF;">Temperaturbereich:</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">-   Betriebsbereich		: 0 °C bis 60 °C</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">-   Lagerbereich		: -5 °C bis 65 °C</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="text-indent:-177pt;margin-left:177pt;">
                          <span style="background:#FFFFFF;">Material:</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">-   Sensorkopf		: PVC</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">-   Gehäuseschaft		: V4A Edelstahl 1.4571</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">Schutzart			: IP 68 (bei angeschlossenem Sensoranschlusskabel)</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">Anschluss			: wasserdichter Steckkopf</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">inkl. Standard-Anschlusskabel, mind. 2 m</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">inkl. Zusatzmaterial zum Einbau in angebotenem Messtopf</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="f9433c07-9c79-4903-a44d-52250e4bad1a" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="3fdfa2f3-6529-46e3-967a-e83b383bb531" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Sensor el. Leitfähigkeit/ Temperatur</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3262584" RNoPart="4">
                <RefPerfNo IDRef="GW_3263457" />
                <Qty>2.000</Qty>
                <QU>St</QU>
                <Description ID="e7bf694b-52ca-4bd9-b1ad-0aef147d6760">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Sensor Sauerstoff</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Ausführung gemäß der in Merkblatt DWA-M 256 festgelegten Mindestanforderungen für Messgeräte.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Kalibrierfreier optischer Sauerstoffsensor (Flureszenzprinzip) zum Anschluss an den oberhalb angebotenen Multiparameter-Messumformer.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Ausgestattet mit folgenden Eigenschaften:</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">-   Werkskalibrierung</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   höchste Stabilität (EPRS-Referenzverfahren)</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   lange Lebensdauer (Grünlicht-Technologie)</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   keine Anströmung erforderlich</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   integrierter Blitzschutz</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   unempfindlich gegenüber H2S, Chlor, ionogenen Substanzen</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   auswechselbare Sensorkappe mit gespeicherten Kalibrierdaten</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   automatische Temperaturkompensation</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Digitale Messwertübertragung</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   mit Steckverbindung zum Anschluss des Sensoranschlusskabels</span>
                        </p>
                        <p />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Messbereich (25 °C)		: 0 bis 20 mg O2/l</span>
                          <br />
                          <span style="background:#FFFFFF;">0 bis 200 % Sättigung</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Ansprechzeit (EN ISO 15839)	: t90 (90 % der Endwertanzeige nach) &lt; 150 s</span>
                          <br />
                          <span style="background:#FFFFFF;">t95 (95 % der Endwertanzeige nach) &lt; 200 s</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Messgenauigkeit		: ± 0,05 mg/l, O2 &lt; 1 mg/l</span>
                          <br />
                          <span style="background:#FFFFFF;">± 0,1 mg/l, O2 &gt; 1 mg/l</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Reproduzierbarkeit		: 0,05 mg/l</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="text-indent:-177pt;margin-left:177pt;">
                          <span style="background:#FFFFFF;">Temperaturbereich:</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">-   Betriebsbereich		: -5 °C bis 50 °C</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">-   Lagerbereich		: -25 °C bis 60 °C</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Druckfestigkeit		: max. 10 bar</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">Material			: Membran-/ Sensorkopf, Schutzkorb: POM, PVC, Silicon</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Gehäuseschaft		: V4A Edelstahl 1.4571</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">Schutzart			: IP 68 (bei angeschlossenem Sensoranschlusskabel)</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">Anschluss			: wasserdichter Steckkopf</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">inkl. Standard-Anschlusskabel, mind. 2 m</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">inkl. Zusatzmaterial zum Einbau in angebotenem Messtopf</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="b9627d53-16be-4347-9d7a-6e4faeedb84b" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="52b91292-d1c1-469e-98af-19febee4f4d5" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Sensor Sauerstoff</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3262585" RNoPart="5">
                <RefPerfNo IDRef="GW_3263457" />
                <Qty>2.000</Qty>
                <QU>St</QU>
                <Description ID="91184783-3cb3-47e9-8a9f-acbc87af7212">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Sensor Trübung</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Ausführung gemäß der in Merkblatt DWA-M 256 festgelegten Mindestanforderungen für Messgeräte.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Digitaler Trübungs-/ Feststoffsensor zum Anschluss an den oberhalb angebotenen Multiparameter-Messumformer.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Ausgestattet mit folgenden Eigenschaften:</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Ultraschall-Reinhaltungssystem</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Nephelometrische Messung gemäß DIN EN 27027, EN ISO 7027, ISO 7027</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   kratzfeste Saphir-Messfenster</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Sensorüberwachungsfunktion</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   integrierter Blitzschutz </span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   mit Schraub-/ Steckverbindung zum Anschluss des Sensoranschlusskabels</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Messbereich (wählbar):</span>
                        </p>
                        <p style="tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">-   Trübungsmessung 		: 0 bis 4 000 FNU/NTU/TEF</span>
                        </p>
                        <p style="tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">-   Feststoffmessung		: 0 bis 4 000 mg/l (ppm)</span>
                        </p>
                        <p style="tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">-   SiO2			: 0 bis 400 g/l</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Trockensubstanz TS (materialabhängig)</span>
                        </p>
                        <p />
                        <p style="text-indent:-177pt;margin-left:177pt;">
                          <span style="background:#FFFFFF;">Verfahrensvariationskoeffizient</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm;">
                          <span style="background:#FFFFFF;">nach DIN 38402 Teil 51	: im Bereich bis 2 000 FNU &lt; 1 %</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="text-indent:-177pt;margin-left:177pt;">
                          <span style="background:#FFFFFF;">Wiederholbarkeit oder </span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;">
                          <span style="background:#FFFFFF;">Wiederholgrenze nach </span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm;">
                          <span style="background:#FFFFFF;">DIN ISO 5725 bzw. DIN 1319	: &lt; 0,015 % bzw. minimal 0,006 FNU</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="text-indent:-177pt;margin-left:177pt;">
                          <span style="background:#FFFFFF;">Temperaturbereich:</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">-   Betriebsbereich		: 0 °C bis 60 °C</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm;">
                          <span style="background:#FFFFFF;">-   US-Reinhaltungssystem	: 0 °C bis 40 °C (Überhitzungsschutz)</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">-   Lagerbereich		: -5 °C bis 65 °C</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="text-indent:-177pt;margin-left:177pt;">
                          <span style="background:#FFFFFF;">Material:</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">-   Messfenster		: Saphir</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">-   Gehäuseschaft		: V4A Edelstahl 1.4571</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">Schutzart			: IP 68 (bei angeschlossenem Sensoranschlusskabel)</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">Anschluss			: wasserdichter Steckkopf</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">inkl. Standard-Anschlusskabel, mind. 2 m</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">inkl. Zusatzmaterial zum Einbau in angebotenem Messtopf</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="df18f556-9fe1-4f5e-900f-dc70b9ff47c9" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="5a5ce914-b903-4026-a7c7-e16c073f3af8" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Sensor Trübung</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3262687" RNoPart="6">
                <RefPerfNo IDRef="GW_3263457" />
                <Qty>2.000</Qty>
                <QU>St</QU>
                <Description ID="c7595dc7-8d1f-4589-9859-024f6a77d121">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Durchflussmesstopf</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Durchflussmesstopf zur Aufnahme der oberhalb angebotenen Sensoren; speziell für kontinuierliche Messungen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Für den Betrieb mit Analysenautomaten ist ein Anschluss zur Versorgung vorgesehen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Inklusive passender Sensorflansche zum Einbau der Sensoren.</span>
                        </p>
                        <p />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Durchflussmenge		: ca. 1,5 cbm/h</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Wassersäule		: mind. 300 mm bis max. 425 mm</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Zulauf Probe		: Schlauchtülle Durchmesser 20 mm</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Ablauf zum Analyzer		: Schlauchtülle Durchmesser 16 mm</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Ablauf/ Überlauf		: HT Rohr Durchmesser 40 mm</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Deckel f. Messfühler		: Aufnahmefläche 300 mm i.D.</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;" />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">Maße			: 340 mm i.D., ca. 760 mm (Höhe über alles)</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">inkl. Zusatzmaterial zum Einbau des Durchflussmesstopfes</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="3dd97673-c143-4192-a491-c700ee25054f" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Hersteller	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="681d255e-8719-4f57-9644-170830d83ec8" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Typ	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Durchflussmesstopf</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053531" RNoPart="7">
                <RefPerfNo IDRef="GW_3263457" />
                <Qty>2.000</Qty>
                <QU>St</QU>
                <Description ID="0d011516-a1d1-47a8-8833-6c8dc2d78436">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Ansteuerbares 2-Wege-Regelventil</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Lieferung, Installation und Inbetriebnahme eines elektronisch ansteuerbaren Regelventils zur Durchflussregulierung. Das Ventil ist in die angebotene PVC-U-Rohrleitung zu integrieren und muss über das angebotene Automatisierungsgerät vom Typ Siemens S7-1500 elektronisch angesteuert und geregelt werden können.</span>
                        </p>
                        <p />
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm 60mm;">
                          <span style="background:#FFFFFF;">Ventiltyp			: elektronisches Regelventil (z. B. Kugelhahn, Membranventil oder ähnlicher Ventiltyp, der für die Durchflussregelung geeignet ist)</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Material Ventilgehäuse		: geeignetes korrosionsbeständiges Material (z. B. PVC-U oder PVDF), kompatibel mit der angebotenen PVC-U-Rohrleitung</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Dichtungsmaterial		: geeignet für den Transport der jeweiligen Medien, chemisch beständig und langlebig (z. B. EPDM, FKM oder PTFE)</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Ansteuerung		: elektronisch über ein 4 - 20 mA Signal, kompatibel mit Siemens S7-1500</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Regelcharakteristik		: proportionale Durchflussregelung mit hoher Präzision zur Anpassung des Durchflusses im Bereich von 0 - 100 %</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm;">
                          <span style="background:#FFFFFF;">maximaler Betriebsdruck	: entsprechend der Druckstufe der Rohrleitung (mind. PN 10)</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm;">
                          <span style="background:#FFFFFF;">maximale Betriebstemperatur	: mindestens 60 °C, kompatibel mit den Einsatzbedingungen der PVC-U-Rohrleitung</span>
                        </p>
                        <p style="text-indent:-177pt;margin-left:177pt;tab-stops:20mm;">
                          <span style="background:#FFFFFF;">Durchflussregelbereich	: der Nenndurchfluss muss präzise und stabil über den gesamten Regelbereich einstellbar sein</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">inkl. aller benötigten Anschlussteile und Adapter</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">inkl. aller benötigten elektrischen Anschlüsse und Signalgeber für die Ansteuerung über die Siemens S7-1500</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">inkl. Unterstützung bei der Inbetriebnahme und Kalibrierung</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Ansteuerbares 2-Wege-Regelventil</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053532" RNoPart="8">
                <RefPerfNo IDRef="GW_3263457" />
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="45cd8e06-cbf5-4f88-8a18-3b901f535595">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Weiteres Material zur Installation der Messtechnik</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Rohrelemente, Verschraubungen, Dichtungen und zusätzliche Installations- und Kleinmaterialien, welche zu einem fachgerechten Einbau der Messtechnik nötig sind. </span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Zur Kalkulation sind eine Gesamtleitungslänge von 20 m, ein Rohrdurchmesser von DN 40 und ein Druck von PN 10 anzunehmen. Als Material für die Rohrelemente ist PVC-U vorzusehen. Die Dichtungen sind entsprechend des zu führenden Mediums zu wählen.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Weiteres Material zur Installation der Messtechnik</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053533" RNoPart="9">
                <RefPerfNo IDRef="GW_3263457" />
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="5706aefd-8602-4703-bb54-fdb1f3033867">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Einbau/ Anbindung der Messtechnik</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Einbau aller oberhalb angebotenen Komponenten parallel zum Bestand und Umbau an endgültigen Standort nach erfolgreichem Probebetrieb.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Inkl. aller mechanischer Arbeiten, inkl. Einbau der Sensoren in den Messtopf und Kalibrierung, inkl. Anbindung der Messumformer und der Ventile an die S7-1500</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">einschließlich aller sonstigen Arbeiten, die für die Erneuerung der beschriebenen Messeinrichtung nötig sind</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Einbau/ Anbindung der Messtechnik</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
            </Itemlist>
          </BoQBody>
        </BoQCtgy>
        <BoQCtgy ID="GW_3789939" RNoPart="9">
          <LblTx>
            <p>
              <span style="background:#FFFFFF;">Demontage/ Rückbau</span>
            </p>
          </LblTx>
          <NotApplBoQ>No</NotApplBoQ>
          <BoQBody>
            <Itemlist>
              <Item ID="GW_3789940" RNoPart="1">
                <RefDescr>Ref</RefDescr>
                <Qty>5.000</Qty>
                <QU>St</QU>
                <Description ID="a5f56759-ffd7-4bc2-a349-acc07d5e615d">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Rückbau von komplexen Komponenten aus z. B. Schaltanlagen, sofern dieses nicht in anderen Positionen enthalten ist. Eine Demontage erfolgt erst nach Beendigung des Probebetriebs.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Dazu gehören beispielsweise:</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">-   Unterstationen mit E/A-Ebene</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Hardware-Regler (z. B. SIPART)</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Fernwirktechnik (z.B. SINAUT)</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die vorhandene Verdrahtung sowie die Dokumentation sind entsprechend anzupassen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Als Pauschalfestpreis pro o. g. Komponente</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Rückbau komplexer Komponenten</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3789941" RNoPart="2">
                <RefDescr>Rep</RefDescr>
                <RefRNo IDRef="GW_3789940" />
                <Qty>5.000</Qty>
                <QU>St</QU>
                <Description ID="e5675e58-acc2-4240-bd2f-37e2f51517b2">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Rückbau von einfachen Komponenten</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">dazu gehören beispielsweise:</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">-   Schütze</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   LS-Schalter</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">-   Mess-Sensor</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die vorhandene Verdrahtung sowie die Dokumentation sind entsprechend anzupassen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Als Pauschalfestpreis pro o. g. Komponente</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Rückbau einfacher Komponenten</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3789942" RNoPart="3">
                <RefDescr>Ref</RefDescr>
                <Qty>25.000</Qty>
                <QU>m</QU>
                <Description ID="3e74f482-4d60-48ae-a1a1-63d2b3f92054">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Abklemmen, demontieren und herausziehen von Installationsleitungen, Steuerleitungen und Leistungskabeln bis zu einem Durchmesser von 16 mm, inkl. evtl. notwendigem Schneiden</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Demontieren, abfahren und entsorgen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die vorhandene Verdrahtung sowie die Dokumentation sind entsprechend anzupassen.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Abklemmen, demontieren, herausziehen Inst.leitungen bis 16 mm Ø</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3789943" RNoPart="4">
                <RefDescr>Rep</RefDescr>
                <RefRNo IDRef="GW_3789942" />
                <Qty>5.000</Qty>
                <QU>m</QU>
                <Description ID="5286ba9e-3967-4e68-9cc9-b7357d21b374">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Abklemmen, demontieren und herausziehen bis zu einem Durchmesser von 28 mm</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Demontieren, abfahren und entsorgen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die vorhandene Verdrahtung sowie die Dokumentation sind entsprechend anzupassen.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Abklemmen, demontieren, herausziehen Inst.leitungen bis 28 mm Ø</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
            </Itemlist>
          </BoQBody>
        </BoQCtgy>
        <BoQCtgy ID="GW_3789952" RNoPart="10">
          <LblTx>
            <p>
              <span style="background:#FFFFFF;">Pflichtenheft</span>
            </p>
          </LblTx>
          <NotApplBoQ>No</NotApplBoQ>
          <BoQBody>
            <Itemlist>
              <PerfDescr ID="GW_3789953">
                <PerfNo>19</PerfNo>
                <PerfLbl>Pflichtenheft</PerfLbl>
                <Description ID="143ee5d3-dd1e-4b95-87b0-a7e368259943">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Für die Gesamtanlage ist die Erarbeitung eines Pflichtenheftes erforderlich. Für die Erstellung des Pflichtenheftes ist der Auftragnehmer verantwortlich.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Das Pflichtenheft ist nach den Erfordernissen mehrmals zu aktualisieren und fortzuschreiben. Das fertige Pflichtenheft bedarf der Genehmigung des Auftraggebers und ist vor den Inbetriebnahmen nach dem Ist-Stand der Anlage vorzulegen. Das Erstellen muss, soweit zutreffend, nach VDI/VDE-Richtlinie 3694 bzw. in Anlehnung an diese Richtlinie erfolgen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Bei der Pflichtenhefterstellung sind die Vorbemerkungen zu diesem LV und die Anlagenbeschreibungen zu berücksichtigen. Das Pflichtenheft ist in elektronischer Form (vorzugsweise Office) und als Download sowie 1-fach in Papierform auszuliefern.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Das Pflichtenheft ist entsprechend der Terminplanung vorzulegen und muss vom Auftraggeber zur Ausführung freigegeben werden. Notwendige Revisionen sind innerhalb von 5 Werktagen beim Auftraggeber vorzulegen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Im Rahmen des Pflichtenheftes sind alle Details hinsichtlich der Aufgabenstellung und der besonderen Anforderungen zu klären und der Lösungsweg umfassend darzustellen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Gegebenenfalls ist das Pflichtenheft im Rahmen der technischen Klärungsphase entsprechend den Erfordernissen zu überarbeiten und dem Auftraggeber erneut vorzulegen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Umfang und Inhalt des Pflichtenheftes</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Zum Umfang des Pflichtenheftes gehören im Wesentlichen:</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Funktionsbeschreibung aller Komponenten in gemeinsamer Zusammenwirkung</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Erstellung der Informationslisten/ Datenpunktlisten</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   aktualisierte Antriebs- und Messstellenlisten</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Maßnahmen zur Qualitätssicherung und Sicherstellung der Einhaltung der Vorgaben dieser Leistungsbeschreibung</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Spezifikation der durchzuführenden Vorbereitungen</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Spezifikation der durchzuführenden Arbeiten und Umbauabläufe</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Spezifikation der Teilfunktion während der Umschlussarbeiten</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Spezifikation der durchzuführenden Funktionstests</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Abnahmespezifikationen</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Detailterminplan, einschließlich Fortschreibung</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Ausführung der Dokumentation</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Konfigurationszeichnungen</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Schrankaufbaupläne</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Stromlaufpläne</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   IT-Sicherheitsrichtlinien mit Bezug auf BSI-Richtlinien und PLS-Sicherheitshandbücher</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="text-decoration:underline;background:#FFFFFF;">Pflichtenheft</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </PerfDescr>
              <Item ID="GW_3053541" RNoPart="1">
                <RefPerfNo IDRef="GW_3789953" />
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="6e9e0724-7cbd-4845-b9fb-1346f2fc5214">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Pflichtenheft</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">für die Gesamtmaßnahme entsprechend aller Vorgaben der Ausführungsbeschreibung, den Vortexten und der Leistungsbeschreibung </span>
                        </p>
                        <p style="text-indent:-14pt;margin-left:14pt;" />
                        <p>
                          <span style="background:#FFFFFF;">als Pauschalfestpreis</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Pflichtenheft</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
            </Itemlist>
          </BoQBody>
        </BoQCtgy>
        <BoQCtgy ID="GW_3053535" RNoPart="11">
          <LblTx>
            <p>
              <span style="background:#FFFFFF;">Inbetriebnahme und Dokumentation</span>
            </p>
          </LblTx>
          <NotApplBoQ>No</NotApplBoQ>
          <BoQBody>
            <Itemlist>
              <PerfDescr ID="GW_3053536">
                <PerfNo>20</PerfNo>
                <PerfLbl>Inbetriebnahme und Dokumentation</PerfLbl>
                <Description ID="8394863e-ed9b-4fbd-b2db-46513703db3b">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Hinsichtlich der seitens des Auftragnehmers zu erbringenden kompletten Ingenieurleistungen wird insbesondere auch auf die Vertragsbedingungen und die Angaben zur Ausführung hingewiesen, mit sämtlichen darin aufgeführten diesbezüglichen Einzelheiten.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Alle weiteren technischen Detailklärungen haben im Zuge der Detailplanungsphase seitens des Auftragnehmers in den erforderlichen Projektbesprechungen mit dem Auftraggeber sowie dem Ing.-Büro nach Erfordernis zu erfolgen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Es sind für die gesamte Abwicklungsphase die kompletten Ingenieurleistungen anzubieten.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Alle nachfolgenden Leistungen verstehen sich als vollständige Inbetriebnahme des SCADA-Systems und des Automatisierungsgerätes sowie der IT-Infrastruktur der Gesamtmaßnahme. Die Inbetriebnahme ist gemeinsam mit dem Auftraggeber in der RUSt Mainz-Wiesbaden durchzuführen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Vorbereitung und Durchführung der Inbetriebnahme des gesamten Leistungsumfangs gemeinsam mit dem Betriebspersonal. Funktions- und Störmeldetests der Anlagen einschließlich evtl. erforderlicher Korrekturen und/oder Nachbesserungen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Es ist ein ausführliches Inbetriebnahmeprotokoll zu erstellen. Mindestens sind folgende Angaben in das Protokoll aufzunehmen:</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Beteiligte</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Daten und Zeiten</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Inbetriebnahmebedingungen</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Befehle, Meldungen, Sollwerte und Einstellungen</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Ergebnisse der Inbetriebnahme (im Fehlerfall auch Angaben zur Ursache)</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Im Zuge der Inbetriebnahme erfolgt die Einweisung des Fachpersonals des Bauherrn in die installierte Systemtechnik und in die Dokumentationsunterlagen. Die Einweisung hat der Auftragnehmer zu protokollieren und sich vom Auftraggeber bestätigen zu lassen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Spätestens 3 Wochen vor dem festgelegten Inbetriebnahmetermin hat der Auftragnehmer eine Checkliste vorzulegen, die von der Projektleitung überprüft wird. Anhand der Checkliste werden die Einweisungen Punkt für Punkt vorgenommen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Der Abschluss der Inbetriebnahme ist von der Projektleitung des Auftraggebers zu bestätigen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Sämtliche Nebenkosten wie Unterbringung, Reisekosten und Verpflegung sind mit einzukalkulieren.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Inbetriebnahme und Dokumentation</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </PerfDescr>
              <Item ID="GW_3053538" RNoPart="1">
                <RefPerfNo IDRef="GW_3053536" />
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="9410e522-1c64-4b35-9b82-983f8fb31818">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Inbetriebnahme der IT/OS-Infrastruktur (Server, Netzwerkkomponenten, Datenübermittlung etc.)</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">als Pauschalfestpreis</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Inbetriebnahme der IT/OS-Infrastruktur</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053540" RNoPart="2">
                <RefPerfNo IDRef="GW_3053536" />
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="eaf6b75d-ccec-4312-b635-a0222313ff05">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Inbetriebnahme der Bedienebene</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">des neuen SCADA-Systems mit dem Automatisierungsgerät</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">als Pauschalfestpreis</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Inbetriebnahme Bedienebene</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053516" RNoPart="3">
                <RefPerfNo IDRef="GW_3053536" />
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="ab99385a-7dc7-4fec-a1c9-3f8e24d072df">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Inbetriebnahme Automatisierungstechnik</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die Inbetriebnahme und der dazugehörige Datenpunkttest sind durchgängig bis zum Leitsystem durchzuführen. Die Ergebnisse sind zu protokollieren. Eine zusätzliche Vergütung erfolgt nicht; daher ist der Aufwand in diese Position mit einzukalkulieren.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Als Pauschalfestpreis</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Inbetriebnahme Automatisierungstechnik</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3262794" RNoPart="4">
                <RefPerfNo IDRef="GW_3053536" />
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="9e65c01e-bf54-4d2f-8bd5-855136efbe7a">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Inbetriebnahme Messtechnik</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">inkl. aller Sensoren und Aktoren des Lieferumfangs, Kalibrierung der Sensoren und einem Datenpunkttest durchgängig bis zum Leitsystem. Die Ergebnisse sind zu protokollieren. Eine zusätzliche Vergütung erfolgt nicht; daher ist der Aufwand in diese Position mit einzukalkulieren.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Als Pauschalfestpreis</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Inbetriebnahme Messtechnik</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3789956" RNoPart="5">
                <RefPerfNo IDRef="GW_3053536" />
                <Qty>4.000</Qty>
                <QU>Wo</QU>
                <Description ID="69bce912-da74-4d50-a006-2ddffa9b55a4">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Probebetrieb mit Bereitschaftsdienst</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Im Anschluss an die Inbetriebnahme wird vor der Abnahme ein Probebetrieb durchgeführt, in dem der Betrieb des Prozessleitsystems optimiert wird.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Während des Probebetriebs des Prozessleitsystems für die Dauer von vier Wochen hat der Auftragnehmer für den Fall einer Störung seiner errichteten Anlagen innerhalb von </span>
                          <span style="font-weight:bold;background:#FFFFFF;">acht Stunden</span>
                          <span style="background:#FFFFFF;"> nach Benachrichtigung zur Störungsbeseitigung anzutreten und diese nach Möglichkeit innerhalb von 24 Stunden zu beseitigen. Andernfalls gilt der Probebetrieb als abgebrochen und muss wiederholt werden. Diese Wiederholung wird nicht vergütet.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Der Zeitraum des Probebetriebs ist schriftlich mit dem Auftraggeber abzustimmen. Der Probebetrieb kann erst nach vollständiger und mängelfreier Inbetriebnahme aller Anlagenteile erfolgen. Der Abschluss des Probebetriebs wird durch den Auftraggeber freigegeben.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Sämtliche Nebenkosten, wie Reisekosten, Spesen usw. sind einzukalkulieren. Die evtl. erforderlichen Einsätze werden nicht gesondert vergütet. Dies gilt auch für Verlängerungen, die der Auftragnehmer zu vertreten hat.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Probebetrieb mit Bereitschaftsdienst</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053542" RNoPart="6">
                <RefPerfNo IDRef="GW_3053536" />
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="def76dab-c526-45bc-84f2-a63bff7b0188">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Komplette ingenieurmäßige Projektabwicklung</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">mit sämtlichen auftragnehmerseitigen Leistungen für Detailplanung, Kabelverlegung, Installation etc. zur Gesamtabwicklung und Erstellung einer betriebsfertigen Anlage.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Im Wesentlichen:</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">Komplette anlagenseitige Klärungen und Koordinierungen, Abstimmung der Schnittstellen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Teilnahme des Projektleiters und des Projektmitarbeiters für Prozessleit- und Automatisierungstechnik bzw. deren Stellvertreter, an allen erforderlichen Projektbesprechungen (2-wöchig) im Zuge der Werks- und Montageplanung sowie weiteren Abstimmungen mit dem Betrieb.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Terminliche und fachtechnische Überwachung sämtlicher Liefer- und Montageleistungen (firmeneigene Projektleistung).</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Sämtliche Details sind mit dem Auftraggeber bzw. dem Ing.-Büro abzustimmen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Bearbeitung und Abstimmung erforderlicher Anträge für die mit der Projektabwicklung erforderlichen Maßnahmen (Behörden, EVU etc.).</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Des Weiteren:</span>
                        </p>
                        <p>
                          <span style="background:#FFFFFF;">Projektbegleitende Dokumentation bis zur endgültigen umfassenden Dokumentation der Anlage.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Als Pauschalfestpreis</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Komplette ingenieurmäßige Projektabwicklung</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053543" RNoPart="7">
                <RefPerfNo IDRef="GW_3053536" />
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="5114edd2-eb57-46cc-8024-6df231978212">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Dokumentation nach Fertigstellung für die Gesamtanlage</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Pläne für elektrische und informationstechnische Leitungen sind als Ausdruck in DIN A4 2-fach und 1-fach in laminierter Form in separatem Ordner auszuführen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Pläne für elektrische und informationstechnische Leitungen sind mit EPLAN P8 in aktueller Version zu erstellen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Der strukturelle Aufbau ist mit dem Auftraggeber abzustimmen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Zusätzlich sind alle Dokumente, Zeichnungen, Stromlaufpläne etc. in 2-facher Ausfertigung in elektronischer Form zu übergeben.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Zulässige Formate sind:</span>
                        </p>
                        <p />
                        <p style="text-indent:-14pt;margin-left:14pt;">
                          <span style="background:#FFFFFF;">-   MS-Word, vorzugsweise aktuellste Version, mind. 2016 </span>
                        </p>
                        <p style="text-indent:-14pt;margin-left:14pt;">
                          <span style="background:#FFFFFF;">-   MS-Excel, vorzugsweise aktuellste Version, mind. 2016 </span>
                        </p>
                        <p style="text-indent:-14pt;margin-left:14pt;">
                          <span style="background:#FFFFFF;">-   Portable Dokument Format (pdf)</span>
                        </p>
                        <p style="text-indent:-14pt;margin-left:14pt;">
                          <span style="background:#FFFFFF;">-   Zeichnungen im AutoCAD-dwg-Format</span>
                        </p>
                        <p style="text-indent:-14pt;margin-left:14pt;">
                          <span style="background:#FFFFFF;">-   Pläne für elektrische und informationstechnische Leitungen in EPLAN P8 und zusätzlich als Export als pdf-Datei</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die Dokumentation enthält die Erstellung und Aktualisierung aller nachstehend geforderten Unterlagen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Für die Gesamtanlage, jede angepasste Unterverteilung, jeden angepassten Messschrank usw.:</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Übersichtspläne der Prozessleittechnik in laminierter Form</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Stromlaufpläne und 1 Satz in laminierter Form in separatem Ordner für Schaltanlage</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Klemmenpläne</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Kabellisten</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Stücklisten in EPLAN- und Excel-Format</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Messlisten überarbeitet und ergänzt</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Infolisten überarbeitet und ergänzt</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Aufbau- und Aufstellungszeichnungen</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Geräte-/ Ersatzteillisten mit Angabe der Typenbezeichnung, Fabrikat, Bestell-Nr. usw.</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Technische Unterlagen, Anschlusspläne, Maßbilder, Betriebs- und Wartungsanleitungen aller gelieferten Teile und Geräte in separaten Ordnern</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Steuerungs- und Funktionsbeschreibungen unter Berücksichtigung der während der Detailplanung aufgetretenen Änderungen</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Checklisten für alle Stör- und Betriebsmeldungen mit Angabe der Ursachen und Hinweisen zur Fehlerbeseitigung</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Darstellung des Verfahrensschemas (R&amp;I)</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   komplette Patchbelegung aufbauend auf der strukturierten Dokumentation des Netzwerkes</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Für das Automatisierungsgeräte-System:</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   dokumentierter Datenpunkttest</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   dokumentierter Kalttest</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   dokumentierter Probebetrieb</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Checklisten für alle Stör- und Betriebsmeldungen mit Angabe der Ursachen und Hinweisen zur Fehlerbeseitigung</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Listen aller einstellbaren Zeiten und Grenzwerte mit dem Bediengerät in tabellarischer Form mit Angabe der Einstellwerte, des Datums der Erstellung und der Änderung</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Für das SCADA-System:</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Dokumentation aller Hardwarekomponenten</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Dokumentation aller Softwarekomponenten (wo ist was installiert und autorisiert)</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Dokumentation aller parametrierten Leistungen (auch Ersatzwertdokumentation)</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Backup des letzten aktuellen Standes des SCADA-Systems (für ein Desaster Recovery - Datenbasis und Software). Der Auftraggeber behält sich vor, ein Desaster Recovery mit Hilfe der erstellten Backups durchzuführen.</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   komplette Quelle der Bausteine</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Handbücher in deutscher Sprache für alle gelieferten Softwarepakete</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Liste aller über SCADA-System einstellbaren Werte</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   farbige Ausdrucke aller Prozessbilder</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Beschreibung des Umgangs (Anwenderhandbuch für die Wartenfahrer) mit dem eingerichteten System</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Anweisungsliste zur Beseitigung von Störungen und Fehlern</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Durchführungsbeschreibung für die Erstellung von Backups, Systemwiederherstellung, Aktualisierung des Whitelistening, Windows- und SCADA-System-Patchmanagement, Aktualisierung Virenpattern</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   überarbeiteter und ergänzter Konfigurator des SCADA-Systems</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   aktuellen Stand der Datenpunktliste</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Auflistung aller Messstellen mit Variablennamen und entsprechenden Bildnamen, wo die entsprechende Messstelle eingebaut ist</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   komplette Dokumentation von allen verwendeten Skripten mit Kommentaren; jede Programmzeile ist zu kommentieren </span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">als Pauschalfestpreis</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Dokumentation nach Fertigstellung für die Gesamtanlage</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
            </Itemlist>
          </BoQBody>
        </BoQCtgy>
        <BoQCtgy ID="GW_3789955" RNoPart="12">
          <LblTx>
            <p>
              <span style="background:#FFFFFF;">Baustelleneinrichtung und Stundenlöhne</span>
            </p>
          </LblTx>
          <NotApplBoQ>No</NotApplBoQ>
          <BoQBody>
            <Itemlist>
              <Item ID="GW_3053544" RNoPart="1">
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="f4b53578-2d9c-468c-8db5-4d5165f7136f">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Baustelleneinrichtung ,-unterhaltung und -räumung</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Baustelleneinrichtung mit Lagerräumen, Baustromversorgung, Wasserversorgung, Personalaufenthalts- und Sanitätseinrichtungen, Beleuchtungsmittel, Transportmittel, Hebezeuge, Bühnen und Gerüste, einschließlich der Räumung für die Maßnahme.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Baustelle gemäß den Leistungen und Fristen einrichten. Zur Einrichtung gehören u. a. Fahrzeuge, Maschinen, Geräte, Werkzeuge, Büro-Container (Auftragnehmer) für die Maßnahme.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Im Zufahrtsbereich sowie im ganzen Gebäude ist durch den Betrieb mit Behinderungen zu rechnen. Erschwernisse dadurch sind in die jeweiligen Einheitspreise einzurechnen. Alle Tätigkeiten des Auftragnehmers, die eine Koordination zwischen ihm und dem Auftraggeber auf dem Gelände verlangen, hat der Auftragnehmer zu berücksichtigen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">In die Baustellenunterhaltung sind die zeitabhängigen Gemeinkosten der Baustelleneinrichtung einzurechnen. Zwischen-, An- und Abtransport sowie Zwischenverschiebungen sind Sache des Unternehmers und ebenfalls hier einzurechnen, soweit sie nicht ausdrücklich in den Einzelpositionen auszuweisen sind. Die Vorhaltung der Baustelleneinrichtung ist für die vertraglich vereinbarte Zeit vorzusehen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Abschließend ist die Baustelle von allen Geräten, Anlagen, Einrichtungen und dergleichen zu räumen. Benutzte Flächen, Wege, entsprechend dem ursprünglichen Zustand ordnungsgemäß herrichten und Verunreinigungen beseitigen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Als Pauschalfestpreis</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Baustelleneinrichtung ,-unterhaltung und -räumung</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053545" RNoPart="2">
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="79ed22fb-85f4-42ae-b3fc-fe01195cd02c">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Endreinigung</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die Endreinigung aller Anlagenteile dieser Ausschreibung sowie der Gebäudeteile, die durch die Montagearbeiten betroffen sind, ist nach Abschluss der Montagearbeiten durchzuführen. Es sind alle auftretenden Verschmutzungen direkt zu entfernen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Als Pauschalfestpreis</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Endreinigung</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <PerfDescr ID="GW_3053546">
                <PerfNo>21</PerfNo>
                <PerfLbl>Stundenlohnarbeiten, Sonstiges</PerfLbl>
                <Description ID="78fa6a9e-8ae6-4788-a972-498972232436">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Für Arbeiten, die nicht über EP erfasst werden, auf besondere Anordnung und nach Genehmigung durch den Auftraggeber, nach Bedarf gegen Stundennachweise einschließlich aller Nebenkosten.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die Stundennachweise werden nur akzeptiert, wenn sie dem Auftraggeber spätestens 4 Wochen nach Abschluss der entsprechenden Arbeiten zur Unterschrift vorliegen. Die ausgeführten Arbeiten und die Spezifikation der entsprechenden Fachkraft sind auf dem Stundennachweis darzulegen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Alle Stundensätze verstehen sich inkl. An- und Abreise, evtl. Übernachtungskosten, Kilometerpauschalen, Fahrzeit, Überstundenzuschlag, Schmutzzulage, Sonn- und Feiertagszuschläge sowie aller anderen Lohnnebenkosten.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="text-decoration:underline;background:#FFFFFF;">Stundenlohnarbeiten, Sonstiges</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </PerfDescr>
              <Item ID="GW_3053548" RNoPart="3">
                <RefPerfNo IDRef="GW_3053546" />
                <Qty>50.000</Qty>
                <QU>h</QU>
                <Description ID="cbdf490b-b4bd-4a1f-bee3-13706e7b1df2">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Ingenieurstunden</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Stundenlohnarbeiten durch Arbeitskräfte auf Anordnung des Auftraggebers ausführen. Im Zuschlag sind alle Nebenkosten enthalten.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Ingenieur: Tarifbereich Eisen-, Metall- und Elektrohandwerk</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="2ea205d2-e31d-4fa1-8033-a6ca17c1dbfd" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Tariflohn, zurzeit gültiger Ecklohn	=	</span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail>
                          <span style="background:#FFFFFF;"> €/h</span>
                        </ComplTail>
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="32b4ba72-0f91-4a6f-b4e8-d8242749a62f" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Zuschlag </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail>
                          <span style="background:#FFFFFF;"> v. H.	=	</span>
                          <span style="text-decoration:underline;background:#FFFFFF;">.......................... €/h</span>
                        </ComplTail>
                      </TextComplement>
                      <Text>
                        <br />
                      </Text>
                      <TextComplement ID="0f7eb9d9-1b88-4e6e-9e9f-1be052d2a84a" Kind="Bidder" MarkLbl="62" Empty="Yes">
                        <ComplCaption />
                        <ComplBody>
                          <span style="text-decoration:underline;background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail>
                          <span style="text-decoration:underline;background:#FFFFFF;"> €/h</span>
                        </ComplTail>
                      </TextComplement>
                      <Text>
                        <p style="tab-stops:70mm;">
                          <span style="background:#FFFFFF;">	</span>
                        </p>
                      </Text>
                      <TextComplement ID="1dcbea87-4fa6-466d-8b62-8116dd563a7f" Kind="Bidder" MarkLbl="63" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Verrechnungssatz für Ingenieur	=	</span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail>
                          <span style="background:#FFFFFF;"> €/h</span>
                        </ComplTail>
                      </TextComplement>
                      <Text>
                        <p style="tab-stops:70mm 115mm;">
                          <span style="background:#FFFFFF;">		================</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Ingenieurstunden</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053549" RNoPart="4">
                <RefPerfNo IDRef="GW_3053546" />
                <Qty>20.000</Qty>
                <QU>h</QU>
                <Description ID="860fdcbb-1a4b-4934-8245-2c6e3901ebf9">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Obermonteurstunden</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Stundenlohnarbeiten durch Arbeitskräfte auf Anordnung des Auftraggebers ausführen. Im Zuschlag sind alle Nebenkosten enthalten.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Obermonteur: Tarifbereich Eisen-, Metall- und Elektrohandwerk</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="58cf1012-e5f3-40c7-97ea-5a07b3275e15" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Tariflohn, zurzeit gültiger Ecklohn	=	</span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail>
                          <span style="background:#FFFFFF;"> €/h</span>
                        </ComplTail>
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="3d1b074a-96d6-43f8-abcb-139961272a42" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Zuschlag </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail>
                          <span style="background:#FFFFFF;"> v. H.	=	</span>
                          <span style="text-decoration:underline;background:#FFFFFF;">.......................... €/h</span>
                        </ComplTail>
                      </TextComplement>
                      <Text>
                        <br />
                      </Text>
                      <TextComplement ID="63edc192-fe43-441e-bfa9-5eb1952ffcae" Kind="Bidder" MarkLbl="62" Empty="Yes">
                        <ComplCaption />
                        <ComplBody>
                          <span style="text-decoration:underline;background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail>
                          <span style="text-decoration:underline;background:#FFFFFF;"> €/h</span>
                        </ComplTail>
                      </TextComplement>
                      <Text>
                        <p style="tab-stops:70mm;">
                          <span style="background:#FFFFFF;">	</span>
                        </p>
                      </Text>
                      <TextComplement ID="517a52a7-915f-400c-bfdd-b0e1a9335ddb" Kind="Bidder" MarkLbl="63" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Verrechnungssatz für Obermonteur	=	</span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail>
                          <span style="background:#FFFFFF;"> €/h</span>
                        </ComplTail>
                      </TextComplement>
                      <Text>
                        <p style="tab-stops:70mm 115mm;">
                          <span style="background:#FFFFFF;">		================</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Obermonteurstunden</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3053550" RNoPart="5">
                <RefPerfNo IDRef="GW_3053546" />
                <Qty>40.000</Qty>
                <QU>h</QU>
                <Description ID="9a8eab7d-f97e-4dcf-92af-cfcbc1330112">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Monteurstunden</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Stundenlohnarbeiten durch Arbeitskräfte auf Anordnung des Auftraggebers ausführen. Im Zuschlag sind alle Nebenkosten enthalten.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Monteur: Tarifbereich Eisen-, Metall- und Elektrohandwerk</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="f4c0e13b-8d62-41cd-867b-486ea4160960" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Tariflohn, zurzeit gültiger Ecklohn	=	</span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail>
                          <span style="background:#FFFFFF;"> €/h</span>
                        </ComplTail>
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="71351719-b3da-4a3a-84cc-71eaf8a07f26" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Zuschlag </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail>
                          <span style="background:#FFFFFF;"> v. H.	=	</span>
                          <span style="text-decoration:underline;background:#FFFFFF;">.......................... €/h</span>
                        </ComplTail>
                      </TextComplement>
                      <Text>
                        <br />
                      </Text>
                      <TextComplement ID="0e21b577-0f5e-4fe9-850d-0ad587c0d600" Kind="Bidder" MarkLbl="62" Empty="Yes">
                        <ComplCaption />
                        <ComplBody>
                          <span style="text-decoration:underline;background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail>
                          <span style="text-decoration:underline;background:#FFFFFF;"> €/h</span>
                        </ComplTail>
                      </TextComplement>
                      <Text>
                        <p style="tab-stops:70mm;">
                          <span style="background:#FFFFFF;">	</span>
                        </p>
                      </Text>
                      <TextComplement ID="06fd6ab3-bdc7-437e-88cd-6027d407c3e9" Kind="Bidder" MarkLbl="63" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Verrechnungssatz für Monteur	=	</span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail>
                          <span style="background:#FFFFFF;"> €/h</span>
                        </ComplTail>
                      </TextComplement>
                      <Text>
                        <p style="tab-stops:70mm 115mm;">
                          <span style="background:#FFFFFF;">		================</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Monteurstunden</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Remark ID="GW_3053551">
                <Description ID="440c643f-d6d3-4998-92d3-8b227c8e948f">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Materiallieferungen</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="text-decoration:underline;background:#FFFFFF;">Materiallieferungen</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Remark>
              <Item ID="GW_3053552" RNoPart="6">
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="b9f7b103-b0d1-41da-a9fa-38bb33e306ab">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Für Materiallieferungen, die nicht über Einheitspreise erfasst werden, wird auf den Einstandspreis des Auftragnehmers ein prozentualer Stoffzuschlag für Gemeinkosten, Wagnis und Gewinn in nachfolgend zu benennender Höhe hinzugerechnet.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Der Einstandspreis ist durch Vorlage des Rechnungsbeleges nachzuweisen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Als Belege anerkannt werden Rechnungen von Herstellerwerken, Vertriebsniederlassungen etc., jedoch keine Rechnungen von Subunternehmern, die unmittelbar für den Auftragnehmer (AN) tätig sind.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">An Materialkosten ist ein Einstandspreis von 3.000,- EUR zugrunde zu legen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Der vorgenannte Stoffzuschlag ist kalkuliert mit</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="dd215a02-a23a-4af2-a528-94f31da73b9a" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption />
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail>
                          <span style="background:#FFFFFF;"> % (vom AN einzusetzen).</span>
                        </ComplTail>
                      </TextComplement>
                      <Text>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Somit beträgt der Pauschalpreis</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="db61cd4d-80c1-4524-9748-536d9624d38d" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">EUR 3.000,- x 1,</span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Materiallieferungen nicht über EP erfasst</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
            </Itemlist>
          </BoQBody>
        </BoQCtgy>
        <BoQCtgy ID="GW_3053554" RNoPart="13">
          <LblTx>
            <p>
              <span style="background:#FFFFFF;">Schulungen</span>
            </p>
          </LblTx>
          <NotApplBoQ>No</NotApplBoQ>
          <BoQBody>
            <Itemlist>
              <PerfDescr ID="GW_3053555">
                <PerfNo>22</PerfNo>
                <PerfLbl>Schulung durch Auftragnehmer auf der Anlage</PerfLbl>
                <Description ID="17626a89-e670-4551-b2ab-ba1ba732e514">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Die Durchführung der Schulungen ist im Wesentlichen projektbegleitend geplant. Hierbei sind Schulungen für das Betriebspersonal zeitnah zur Inbetriebnahme durchzuführen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Für jede Schulung ist durch den Auftragnehmer ein Schulungsprogramm zu entwerfen, mit dem Auftraggeber abzustimmen und durch den Auftraggeber freigeben zu lassen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die Schulung ist ca. drei Wochen vorher durch eine Tagesordnung anzukündigen und mit den Teilnehmern abzustimmen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Nach Abstimmung sind Schulungsunterlagen farbig ca. 2 Wochen vor Beginn der Schulung abzugeben.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die Unterlagen sind dem Auftraggeber auf einem Datenträger zu übergeben.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Schulung durch Auftragnehmer auf der Anlage</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </PerfDescr>
              <Item ID="GW_3053557" RNoPart="1">
                <RefPerfNo IDRef="GW_3053555" />
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="d67564b1-6be8-4ca7-a809-3e82a032f638">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Begleitende Unterweisung in die Bedienung des Prozessleitsystems</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Während des Probebetriebs wird nach einem abzustimmenden Zeitplan das Personal auf dem System projektspezifisch geschult.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Es sind die Besonderheiten des Systems zu vermitteln und für den Anwender durchführbare Administrations- und Fehlerbehebungen zu erläutern.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die Einweisung auf das System erfolgt mit Unterlagen, die im Rahmen der Dokumentation zu erstellen sind (Anwenderhandbuch für die Bedienung/ Administration).</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Alle durch die Bediener zu leistenden Arbeiten sollen danach selbstständig durchgeführt werden können. Im Einzelfall sind Einweisungen zu wiederholen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Der Auftragnehmer hat entsprechend Personal für Schulungen vorzuhalten, sodass der Probebetrieb aufrecht erhalten werden kann.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die geleisteten Einweisungen sind anhand von Stundennachweisen unter Angabe der geschulten Personen zu dokumentieren. Falls diese fehlen gilt der Schulungsbedarf des Personals des Auftraggebers als maßgeblich. </span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Auf Wunsch des Auftraggebers sind Teile als Power-Point-Präsentation durchzuführen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die Einweisung ist durch einen geeigneten Fachingenieur des Auftragnehmers einschließlich aller Nebenkosten wie Reise- und Unterbringungskosten des Ausbilders zu kalkulieren.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Es sind bis zu 8 Stunden in Blöcken von 2 bis 4 Stunden, die während des Probebetriebs hierfür aufgewendet werden, einzukalkulieren.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Folgende Themen sind mindestens zu vermitteln:</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Erläuterung der wesentlichen Unterschiede von Bestandssystem und dem angebotenen SCADA-System</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Einweisung in das angebotene SCADA-System</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Systempflege der Server</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Vorgehensweise bei der Datensicherung</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Updates Betriebssystem</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Aktualisierung Virenschutz</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Funktionsweise der Datenübermittlung</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Einweisung Prozessleitsystem</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <PerfDescr ID="GW_3053558">
                <PerfNo>23</PerfNo>
                <PerfLbl>Schulung durch SCADA-System-Hersteller</PerfLbl>
                <Description ID="50c44745-532a-43e4-a153-f377d2399831">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Neben der Schulung des Betriebspersonals durch den Auftragnehmer sollen weitere, externe Schulungen durch den Hersteller des angebotenen SCADA-Systems durchgeführt werden. Der Veranstaltungsort muss in Deutschland liegen.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Schulung durch SCADA-System-Hersteller</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </PerfDescr>
              <Item ID="GW_3053560" RNoPart="2">
                <RefPerfNo IDRef="GW_3053558" />
                <Qty>1.000</Qty>
                <QU>St</QU>
                <Description ID="d09be5f3-48d1-48d7-9926-0d4fdda782f9">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Schulung SCADA-System Basis</span>
                        </p>
                        <p />
                        <p style="tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Dauer		: mind. 2 Tage</span>
                        </p>
                        <p style="tab-stops:20mm 40mm;">
                          <span style="background:#FFFFFF;">Teilnehmer		: 1 Person</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Mit folgenden Inhalten:</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">-   Engineering:</span>
                        </p>
                        <p style="margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Anlagenexplorer</span>
                        </p>
                        <p style="margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Prozessanbindung</span>
                        </p>
                        <p style="margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Bildeditor</span>
                        </p>
                        <p style="margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Berichtserstellung</span>
                        </p>
                        <p style="margin-left:14pt;" />
                        <p>
                          <span style="background:#FFFFFF;">-   Anwender:</span>
                        </p>
                        <p style="margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Bedienung</span>
                        </p>
                        <p style="margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Visualisierung</span>
                        </p>
                        <p style="margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Kurven</span>
                        </p>
                        <p style="margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Meldearchiv</span>
                        </p>
                        <p style="margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Berichte</span>
                        </p>
                        <p style="margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Alarmierungen</span>
                        </p>
                        <p style="margin-left:14pt;" />
                      </Text>
                      <TextComplement ID="55db36cf-b96d-4dd6-9101-9b191e7dea03" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Ort		: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="35016666-b1c3-46ec-b1b0-1900b5a6aa60" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Veranstalter	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                      <Text>
                        <p />
                      </Text>
                      <TextComplement ID="d61c1893-e6eb-4e97-b73a-282b3929cd4e" Kind="Bidder" MarkLbl="62" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Produktbezeichnung	: </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'..........................'</span>
                        </ComplBody>
                        <ComplTail />
                      </TextComplement>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Schulung SCADA-System Basis</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
            </Itemlist>
          </BoQBody>
        </BoQCtgy>
        <BoQCtgy ID="GW_3266775" RNoPart="14">
          <LblTx>
            <p>
              <span style="background:#FFFFFF;">Wartungsvertrag</span>
            </p>
          </LblTx>
          <NotApplBoQ>No</NotApplBoQ>
          <BoQBody>
            <Itemlist>
              <PerfDescr ID="GW_3266776">
                <PerfNo>24</PerfNo>
                <PerfLbl>Wartungs- und Servicevertrag</PerfLbl>
                <Description ID="2e67ace7-b7b5-4d67-b2f0-f94c4ac7db4f">
                  <CompleteText>
                    <ComplTSB>Yes</ComplTSB>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Wartungs- und Servicevertrag für die im Lieferumfang enthaltene Software und elektrischen Bauteile.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Wartungs- und Instandsetzungsarbeiten für 4 Jahre einschließlich sämtlicher Personal- und Fahrkosten, Wegegelder sowie des Materials für Ersatz- bzw. Austauschteile.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Unter Instandhaltung wird die vorbeugende Wartung/ Inspektion (W) und Instandsetzung (im Bedarfsfall) von Hardware verstanden.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Für Instandsetzungsarbeiten von elektrischen Bauteilen, die nicht unter die Gewährleistung fallen und die in den normalen Geschäftszeiten Montag bis Donnerstag von 7:00 Uhr bis 16:00 Uhr und Freitag von 7:00 Uhr bis 12:00 Uhr erfolgen, ist unter Beachtung der preislichen Lohnkosten mit den Zuschlägen für Gemeinkosten, Sozialkassenbeiträgen, vermögenswirksamen Leistungen und dgl. sowie Lohn- und Gehaltsnebenkosten einschließlich aller Nebenkosten wie Reise- und Unterbringungskosten einzurechnen. Die Anzahl der Stunden bezieht sich auf die reine Arbeitszeit vor Ort.</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Serviceunterstützung/ Wartung</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Zur Unterstützung des beim Auftraggeber eingesetzten qualifizierten Personals, zu dessen Aufgaben auch die Überwachung der im LV beschriebenen Systeme gehört, wird folgende Serviceunterstützung geleistet:</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Serviceunterstützung für die Vorbehaltung eines technischen Bereitschaftsdienstes (Personalvorhaltung und Ersatzteilvorhaltung) zur Sicherstellung einer kurzfristigen Durchführung von Instandhaltungsmaßnahmen. Die Serviceleistungen beziehen sich auf den im gesamten Leistungsverzeichnis beschriebenen Umfang.</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Leistungen des Auftragnehmers</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Der Auftragnehmer verpflichtet sich, einen technischen Bereitschaftsdienst für den kurzfristigen Zugriff auf Fachpersonal vorzuhalten.</span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="f71b339d-5865-4df8-8f41-f620248269a5" Kind="Bidder" MarkLbl="60" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">Eine zentrale Leitstelle in </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'.........................'</span>
                        </ComplBody>
                        <ComplTail>
                          <span style="background:#FFFFFF;"> (Ortsangabe, Bieterangabe) gewährleistet die Servicezeit für den Beginn der Störungsbehebung und den Zugriff auf das zentrale Ersatzteillager.</span>
                        </ComplTail>
                      </TextComplement>
                      <Text>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die Personal-/ Ersatzteilanforderung erfolgt jeweils telefonisch oder per E-Mail.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Der Auftraggeber übergibt nach Abnahme eine Liste der Anforderungsberechtigten.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Während der üblichen Arbeitszeit (montags bis donnerstags von 7:00 bis 16:00 Uhr und freitags 7:00 bis 12:00 Uhr) </span>
                        </p>
                        <p />
                      </Text>
                      <TextComplement ID="7d617cf5-e04e-4af7-b59f-6bb2dab74387" Kind="Bidder" MarkLbl="61" Empty="Yes">
                        <ComplCaption>
                          <span style="background:#FFFFFF;">nimmt die </span>
                        </ComplCaption>
                        <ComplBody>
                          <span style="background:#FFFFFF;">'.........................'</span>
                        </ComplBody>
                        <ComplTail>
                          <span style="background:#FFFFFF;"> (Abteilung/Position, Bieterangabe) die Störmeldungen entgegen.</span>
                        </ComplTail>
                      </TextComplement>
                      <Text>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">An Wochenenden und Feiertagen sowie werktags außerhalb der üblichen Arbeitszeit ist die zentrale Leitstelle der Ansprechpartner bei Störungen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Servicezeit</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Servicezeit ist der Zeitraum, in dem der Auftragnehmer die vereinbarte Leistungserbringung zusichert. Der Servicezeitraum ist während der Vertragslaufzeit Montag - Sonntag einschließlich Feiertagen von 0 - 24 Uhr.</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Antrittszeit</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Antrittszeit ist der Zeitraum zwischen Aufforderung des Auftraggebers Servicepersonal zu entsenden (ggf. nach telefonischer Beratung) und dem Eintreffen des Servicepersonals beim Kunden. Die Antrittszeit beträgt max. </span>
                          <span style="font-weight:bold;background:#FFFFFF;">12 h</span>
                          <span style="background:#FFFFFF;">. Bei Nichteinhaltung gilt eine Vertragsstrafe von 250,- Euro als vereinbart.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Bei unvorhergesehenen Ereignissen (Unfall, Stau, Unwetter etc.) kann sich die zugesicherte Antrittszeit verlängern. Die Beweislast trägt der Auftragnehmer.</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Reparaturzeit/ Ersatzteilvorhaltung</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Reparaturen sind unverzüglich nach Fehlererkennung durchzuführen. Der Auftragnehmer ist verpflichtet, alle erforderlichen Ersatzteile in ausreichender Anzahl sowie Mess- und Prüfgeräte zur Fehlersuche vorzuhalten.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die Ersatzteilvorhaltung bezieht sich nur auf Teile, die im Rahmen der Gewährleistung ausgetauscht werden müssen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Vorbeugende Wartung</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Der Auftragnehmer verpflichtet sich, während der Gewährleistungszeit alle vorbeugenden Wartungsarbeiten kostenfrei auszuführen. Der Umfang der vorbeugenden Wartung ist im anliegenden Wartungsvertrag anzugeben.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die Wartung umfasst mindestens:</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Inspektion/ Wartung alle 12 Monate zur Feststellung unzulässiger Abweichungen vom Sollzustand</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Überprüfung der installierten Systeme</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Überprüfung Ereignisanzeigen/Störmeldungen</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Überprüfung der Applikationssoftware</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Installation von Sicherheitsupdates/Patches</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Diese Leistungen sind vor Ort auszuführen und durch schriftliche Belege nachzuweisen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Mit dem Angebot sind ein Wartungsplan und eine Liste mit den zu erwartenden Verbrauchsmaterialien, inkl. aller zusätzlich anfallenden Kosten für Verbrauchsmaterialien, vorzulegen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="text-decoration:underline;background:#FFFFFF;">Maßnahmen des Auftraggebers</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Der Auftraggeber ist verantwortlich für die betrieblich und gesetzlich erforderlichen Sicherheitsmaßnahmen und hat die für die Durchführung der Arbeiten erforderlichen Betriebszustände herzustellen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Der Auftraggeber stellt dem Auftragnehmer – soweit erforderlich – unentgeltlich zur Verfügung:</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   geeignete Ansprechpartner</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   benötigte Unterlagen und Informationen, soweit vorhanden</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   auf Anforderung des Auftragnehmers die aus Gründen des Unfallschutzes erforderliche zweite Person</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Der Auftraggeber stellt dem Auftragnehmer im Bedarfsfall die im Rahmen der normalen Ersatzteilvorhaltung vorhandenen Reserveteile kostenlos zur Verfügung. Die Ersatzteile sind vom Auftragnehmer bei Gebrauch kostenfrei zu ersetzen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Bei Erweiterungen der Anlagen und Einbau von Änderungen ist die zuständige Abteilung zu informieren, damit die laufende Dokumentation und Fortschreibung der Ausgabestände sichergestellt werden kann.</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Folgende Leistungen werden nach Aufwand zu den jeweils gültigen Verrechnungssätzen gesondert in Rechnung gestellt (Preise gemäß Angebot, nach Abnahme gemäß Preisgleitklausel):</span>
                        </p>
                        <p />
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Fehlersuche und Instandsetzung vor Ort, sofern kein Gewährleistungsfall vorliegt</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Aufwand an Fahrten und Wegezeiten, sofern kein Gewährleistungsfall vorliegt</span>
                        </p>
                        <p style="text-indent:-12pt;margin-left:12pt;">
                          <span style="background:#FFFFFF;">-   Ersatz von Teilen, sofern kein Gewährleistungsfall vorliegt</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Den eindeutigen Nachweis, dass der Einsatz nicht in die Gewährleistung fällt, hat der Auftragnehmer zu führen.</span>
                        </p>
                        <p />
                        <p>
                          <span style="font-weight:bold;text-decoration:underline;background:#FFFFFF;">Angebote ohne Wartungsvertragsangebot werden nicht gewertet!</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Wartungs- und Servicevertrag </span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </PerfDescr>
              <Item ID="GW_3266778" RNoPart="1">
                <RefPerfNo IDRef="GW_3266776" />
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="1c3731f9-16d2-470d-a1a2-f0f1df8964fc">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Wartungs- und Servicevertrag für das 1. Jahr</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die Vergütung erfolgt nach Vorlage des Berichtes der durchgeführten Arbeiten für das abgelaufene Jahr.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Wartungs- und Servicevertrag für das 1. Jahr</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3266779" RNoPart="2">
                <RefPerfNo IDRef="GW_3266776" />
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="45ae13e1-c105-446a-9238-b3d4400cbd19">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Wartungs- und Servicevertrag für das 2. Jahr</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die Vergütung erfolgt nach Vorlage des Berichtes der durchgeführten Arbeiten für das abgelaufene Jahr.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Wartungs- und Servicevertrag für das 2. Jahr</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3266780" RNoPart="3">
                <RefPerfNo IDRef="GW_3266776" />
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="7722dbb1-aca1-4b62-bead-cb5f3c6e3045">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Wartungs- und Servicevertrag für das 3. Jahr</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die Vergütung erfolgt nach Vorlage des Berichtes der durchgeführten Arbeiten für das abgelaufene Jahr.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Wartungs- und Servicevertrag für das 3. Jahr</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
              <Item ID="GW_3266781" RNoPart="4">
                <RefPerfNo IDRef="GW_3266776" />
                <Qty>1.000</Qty>
                <QU>psch</QU>
                <Description ID="bb80dc31-4f8e-468a-baf8-2ae510e0eb29">
                  <CompleteText>
                    <DetailTxt>
                      <Text>
                        <p>
                          <span style="background:#FFFFFF;">Wartungs- und Servicevertrag für das 4. Jahr</span>
                        </p>
                        <p />
                        <p>
                          <span style="background:#FFFFFF;">Die Vergütung erfolgt nach Vorlage des Berichtes der durchgeführten Arbeiten für das abgelaufene Jahr.</span>
                        </p>
                      </Text>
                    </DetailTxt>
                    <OutlineText>
                      <OutlTxt>
                        <TextOutlTxt>
                          <p>
                            <span style="background:#FFFFFF;">Wartungs- und Servicevertrag für das 4. Jahr</span>
                          </p>
                        </TextOutlTxt>
                      </OutlTxt>
                    </OutlineText>
                  </CompleteText>
                </Description>
              </Item>
            </Itemlist>
          </BoQBody>
        </BoQCtgy>
      </BoQBody>
    </BoQ>
  </Award>
</GAEB>